5.3.3 Set annual time schedules (holidays)
Overview
This section describes how to set an annual holiday.
While a holiday schedule is active, the controller will be in the OFF-mode!
Other weekly schedules will still be active. It will still be possible to manually override the controller while in holiday
mode.
Up to 12 annual holidays can be programmed (Pr01 to Pr12).
Holiday schedules have priority over weekly schedules.
Requirements
Time scheduler is enabled (see chapter 5.3.1).
Procedure
1.
Press the (
) button longer than 2 seconds.
➔ SEL and the actual Date and Time are displayed alternatingly.
2.
Press the ( ) button briefly to go to the scheduler submenu.
➔ PRO and SEL is displayed.
3.
Press the (
) button: Schedule status indicates whether it is OFF or
ON.
 / 
4.
Press the (
/
➔ When scheduler is ON,
5.
Press the ( ) or ( ) button to select between programs
Pr 01...Pr 12.
6.
Press the (
) button and assign one of the following functions to the
program with the ( ) ( ) button:
no
= Switching time not activated
OP
= Operating mode ON (Occupied), ECO (Unoccupied) or OFF
(protective operation)
LP
= Setpoint of a control loop (setting range 0-100%, °C/°F,
Pascal)
AO
= Positioning of the analog output (output must be in
manual mode!)
FAN
= Fan control (fan stages from FSP0-3 and Auto)
do
= Positioning of the digital output (output must be in manual
mode!)
Hday = Annual time schedule (holiday)
1 bar indicates setting step 1 is executed.
Doc: 70-07-0951A, 20220504
Subjects to alteration
) button to change the status.
is displayed.
© Vector Controls LLC, USA
www.vectorcontrols.com
X2-O
M
PERATIONS
ANUAL
For setting "OP", "LP", "AO", "FAN" and
"do" see chapter 5.3.2.
T
D
OUCH
ISPLAY
Page 13-18