Notifier NOTI-FIRE-NET Manual page 9

Hide thumbs Also See for NOTI-FIRE-NET:
Table of Contents

Advertisement

Overall Limitations
Cable Manufacturer, Part
Number, and Number of Gauges/
Conductors
SIGNAL 82802-06-14, 18 AWG, 1
Pair Unshielded
SIGNAL 98181-06-04, 18 AWG, 1
Pair Unshielded
SIGNAL 962034619, 24 AWG,
3 Pair Unshielded
SIGNAL 962044619, 24 AWG,
4 Pair Unshielded
SIGNAL 962064619, 24 AWG,
6 Pair Unshielded
SIGNAL 962624619, 24 AWG,
4 Pair Unshielded
SIGNAL9669544623, 24 AWG, 4
Pair Unshielded
WEST PENN WIRE D999,
12 AWG, 1 Pair Shielded
Cable Manufacturer,
Part Number,
and Number of
Gauges/Conductors
WEST PENN WIRE 991,
14 AWG, 1 Pair Shielded
WEST PENN WIRE D995, 14
AWG, 1 Pair Shielded
WEST PENN WIRE AQ225,
16 AWG, 1 Pair Unshielded
WEST PENN WIRE AQ294,
16 AWG, 1 Pair Shielded
WEST PENN WIRE D980,
18 AWG, 1 Pair Unshielded
WEST PENN WIRE D975,
18 AWG, 1 Pair Shielded
NOTE: In the event of a panel failure at a wire node, the data is not regenerated locally. The node may be manually bypassed using the NBB-1
Assembly. In this case, the total length of wire becomes the sum of both lengths of wire between operating nodes. If the total length exceeds the
maximum allowable length for a given threshold, the network may lose communication. Separately powered repeater(s) may be employed at each
node in a point-to-point connection to ensure data regeneration.
NOTI•FIRE•NET™ PN 50257:E 7/5/01
Technical Manuals Online! - http://www.tech-man.com
Manufacturer's Specifications
Mid-Cap., FPLP, PVC, NEC
Article 760, UL 1424
Mid-Cap., FPL, PVC, NEC
Article 760, UL 1424
CLZ/CMR
CLZ/CMR
CLZ/CMR
CMR/MRP
CMP/MPP
FPL, PVC, NEC, Article 760, UL
1424 and 1581
Table 3 Twisted Pair Cable Lengths per Cable Segment (2 of 3)
Manufacturer's
Specifications
FPLR, UL 1424 and UL 1666 High:
FPL, PVC, NEC, Article 760,
UL 1424 and 1581
FPL or PLTC
Direct Burial Water Blocked
FPL or PLTC
Direct Burial Water
Blocked
FPL, PVC, NEC Article 760,
UL 1424 and 1581
FPL, PVC, NEC Article 760,
UL 1424 and 1581
Table 4 Twisted Pair Cable Lengths per Cable Segment (3 of 3)
Fiber Optic Circuits
The attenuation of cabling between two nodes/repeaters (fiber optic circuits are point-to-point)
must not exceed a 8 dB limit. If the distance required for a circuit segment is greater than
permitted, a Repeater module (RPT-F) must be inserted into the circuit at intervals less than, or
equal to, the 8 dB attenuation length restriction.
Attenuation Determination:
Find the rated dB loss per foot within the cable manufacturer's specifications. Determine the
total attenuation between the two nodes/repeaters due to the cable.
Loss = (loss/ft.) x (length in feet)
Establish the dB loss for each connector and splice. Sum all the losses.
firealarmresources.com
Permissible Single Twisted Pair Range
Data Threshold:
(In Feet) For Each Cable Segment
All Nodes And/Or
Repeaters On A
Point-To-Point
Cable Segment
2 Nodes/Repeaters
High:
1-1200
Low:
1000-2800
High:
1-1200
Low:
1000-2800
High:
1-1400
Low:
1200-2000
High:
1-1400
Low:
1200-2000
High:
1-1400
Low:
1200-2000
High:
1-1400
Low:
1200-2000
High:
1-1400
Low:
1200-2000
High:
1-800
Low:
800-1400
Permissible Single
Twisted Pair Range (In Feet)
Data Threshold:
For Each Cable Segment
All Nodes And/Or
Repeaters On A
Point-To-Point
Cable Segment
2 Nodes/Repeaters
1-800
Low:
600-1000
High:
1-800
Low:
800-1400
High:
1-1400
Low:
1200-2800
High:
1-1000
Low:
1000-1600
High:
1-1200
Low:
1000-3000
High:
1-800
Low:
800-1400
Bus Configuration
3 to 7 Nodes/Repeaters
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
Bus
Configuration
3 to 7 Nodes/Repeaters
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
1-100
N/A
9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NOTI-FIRE-NET and is the answer not in the manual?

Table of Contents