AJ65FBTA42-16DTE CC-Link System Low Profile Waterproof Type Remote I/O Module User's Manual
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using this equipment, thoroughly read this manual. Also pay careful attention
to safety and handle the module properly.
These precautions apply only to this equipment. Refer to the CPU module user's
manual for a description of the PC system safety precautions.
These
SAFETY PRECAUTIONS
categories: "DANGER" and "CAUTION".
Procedures which may lead to a dangerous condition and
DANGER
cause death or serious injury if not carried out properly.
Procedures which may lead to a dangerous condition and
CAUTION
cause superficial to medium injury, or physical damage
only, if not carried out properly.
Depending on circumstances, procedures indicated by
result in to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever
necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
When a communication error occurs in the data link, the communication error
station will be in the following condition. Configure an interlocking circuit in a
sequence program using the communication status information so that the safety
of the overall system is always maintained.
Accident may occur due to output error or malfunction.
(1) Input points from remote I/O station will be all switched off.
(2) Output points from remote I/O station will be all switched off.
I/O could be switched on or off when a problem occurs in the remote I/O modules.
So build an external monitoring circuit that will monitor any I/O signals that could
cause a serious accident.
Use each module in an environment as specified in the "general specification" in
the CPU module user's manual. Usage of the module outside the general
specification range may cause electric shock, fire, malfunction, product damage or
deterioration.
Do not have control cables and communication cables bundled with or placed near
by the main circuit and/or power cables. Wire those cables at least 100mm(3.94
inch) away from the main circuit and/or power cables. It may cause malfunction
due to noise interference.
[INSTALLATION PRECAUTIONS]
Do not directly touch the module's conductive parts.
Doing so could cause malfunction or trouble in the module.
Tighten the module securely using DIN rail or installation screws within the
specified torque range.
Loose terminal screws may cause a short circuit or erroneous operation. If the
terminal screws are too tight, it may cause falling, short circuit or erroneous
operation due to damage of the screws.
[WIRING PRECAUTIONS]
Completely turn off the externally supplied power used in the system when
installing or placing wiring. Not completely turning off all power could result in
electric shock or damage to the product.
Be sure to ground the FG terminals to the protective ground conductor.
Not doing so could result in electric shock or erroneous operation.
When wiring in the PLC, be sure that it is done correctly by checking the product's
rated voltage and the terminal layout.
Fix the attachment screws of waterproof cap and communication adapter securely
within the specified torque range.
Loose attachment screws may cause a fire or erroneous operation. If the
attachment screws are too tight, it may cause a short circuit or erroneous
operation due to damage of the screws.
Make sure that foreign objects do not get in side the module, such as dirt and wire
chips. It may cause fire product failure or malfunction.
IP67 is only satisfied when the waterproof plug, waterproof cap, and
communication adapter are all connected.
Do not attach the communication cable to the I/O connector, as the I/O connector,
the communication connector and the power supply connector are the same in
shape.
Failure to do so may cause frailer or malfunction of the PLC.
Be sure to fix the wires or cables by ducts or clamps when connecting them to the
module. Failure to do so may cause damage of the module or the cables due to
accidental pull or unintentional shifting of the cables, or malfunctions due to poor
contact of the cable.
Do not install the control lines together with the communication cables, or bring
them close to each other. Failure to do so may cause malfunctions due to noise.
HEAD OFFICE: 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212, JAPAN
classify the safety precautions into two
CAUTION may also
DANGER
CAUTION
CAUTION
DANGER
CAUTION
[WIRING PRECAUTIONS]
When disconnecting a communication or power supply cable from the module, do
not pull on the cable itself.
Disconnect cables not fitted with a connectors by holding and pulling the cable
connector. Disconnect cables not fitted with a connector by removing the screws
from the part connected to the module can cause damage to the module or cable,
or, malfunction due to cable connection faults.
[STARTING AND MAINTENANCE PRECAUTIONS]
Do not touch terminals when the power is on. Doing so could cause an electric
shock.
Switch off all phases of the externally supplied power used in the system when
cleaning the module or retightening the terminal or module mounting screws. Not
doing so could result in electric shock.
Never try to disassemble of modify module. It may cause product failure,
malfunction, fire or cause injury.
Do not drop or apply any strong impact to the module. Doing so may damage the
module.
Completely turn off the externally supplied power used in the system before
mounting or removing the module to/from the panel. Not doing so could result in
damage to the product.
Always make sure to touch the grounded metal to discharge the electricity charged
in the electricity charged in the body, etc., before touching the module.
Failure to do say cause a failure or malfunctions of the module.
[DISPOSAL PRECAUTIONS]
When disposing of this product, treat it as industrial waste.
1. Specification
Item
Number of input points
8 points
Isolation method
Photocoupler
Rated input voltage
24 V DC
Rated input current
Approx. 7 mA
Operating voltage range
20.4 to 26.4 V DC (ripple ratio: within 5 %)
Max. simultaneous ON
100 %
input points
ON voltage/ON current
14 V or higher/3.5 mA or higher
OFF voltage/OFF current 6 V or lower/1.7 mA or lower
Input resistance
Approx. 3.3 k
Response
OFF
ON 1.5 ms or lower (when 24 V DC)
time
ON
OFF 1.5 ms or lower (when 24 V DC)
Input form
Negative common (source type)
Number of output points
8 points
Isolation method
Photocoupler
Rated load voltage
24 V DC
Operating load voltage
20.4 to 26.4 V DC (ripple ratio: within 5 %)
range
Max. load current
1.0 A/point 4.0 A/common
Max. load inrush current
2.0 A 10 ms or lower
Leakage current at OFF
0.3 mA or lower
0.15 V or lower (TYP.) 1.0 A,
Max. voltage drop at ON
0.2 V or lower (MAX.) 1.0 A
Response
OFF
ON 0.5 ms or lower
time
ON
OFF 1.5 ms or lower (resistive load)
Output form
Source type
Overload protection function, overheat protection
Protection function
function LED lights up when protection is occurring.
External power
Voltage 20.4 to 26.4 V DC (ripple ratio: within 5 %)
supply for
15 mA or lower (when 24 V DC, all points ON)
Current
output part
Not including external load current
Surge suppressor
Zener diode
16 points/common (waterproof connector 2 to 4-wire
Wiring method for common
type: input, waterproof connector 2-wire type: output)
Number of stations occupied 1 station 32 points assignment (use 16 points)
I/O module power
Voltage 20.4 to 26.4 V DC (ripple ratio: within 5 %)
supply
Current 45 mA or lower (when 24 V DC, all points ON)
DC type noise voltage 500 Vp-p, noise width 1 µs,
Noise durability
noise frequency 25 to 60 Hz (noise simulator condition)
500 V AC for 1 minute between all DC external
Withstand voltage
terminals and ground
10 M
Ω
Insulation resistance
resistance tester between all DC external terminals and
ground
Protection of degree
IP67
Weight
0.40 kg
Option
Waterproof cap: A6CAP-WP2
For information about the connection devices necessary to use the main module,
see the CC-Link System Small-Type Remote I/O Module User's Manual.
IB-0800180-D
IB No.
AJ65FBTA42-16DTEU
Model
CAUTION
DANGER
CAUTION
CAUTION
Description
Ω
or higher, measured with a 500 V DC insulation
Printed in Japan on recycled paper.
(0706)MEE

Advertisement

loading

Summary of Contents for Mitsubishi Electric AJ65FBTA42-16DTE

  • Page 1 IB-0800180-D IB No. AJ65FBTA42-16DTEU Model HEAD OFFICE: 1-8-12, OFFICE TOWER Z 14F HARUMI CHUO-KU 104-6212, JAPAN AJ65FBTA42-16DTE CC-Link System Low Profile Waterproof Type Remote I/O Module User's Manual • • SAFETY PRECAUTIONS [WIRING PRECAUTIONS] (Read these precautions before using.) CAUTION When using this equipment, thoroughly read this manual.
  • Page 2 2-4.5 6 mounting screw Connector for connection to main module (2.36) 48(1.89) 34 0.5(1.33) 50 1(1.96) 6(0.24) TERMINATION 18.3(0.72) 26.5(1.04) Communication adapter(back) Communication adapter(front) Connector for connection to communication adapter J65FBTA42-16DTE POWER PROTECT Main module Communication STATION NO B RATE adapter 2.