2. Operation and Maintenance

2.2 Home Screen

• Supply Air Temp: The current temperature of the discharge air.
Note: If setting the control mode to Return Air, this setting becomes "Return Air Temp."
• Humidity: The current relative humidity of the return air.
• Dehumidification: The status of the dehumidification system. It will display "ON" when the return air humidity exceeds the
humidity setting + the humidity band.
• Fan: The current total fan speed expressed as a percent of max cumulative airflow.
Note: If max fan speed is set to 80%, for example, the home screen will only show up to 80%.
• Cooling Operation: The current cooling output as a percent of rated capacity.
• Maintenance Mode: The control button to toggle Maintenance Mode. (Must be enabled in user settings.) Refer to
Maintenance Mode section for more information.
• Unit Cooler On/Off: The control button to turn the In-Row Cooler on or off.
• Unit Status: The current cooling status of the In-Row Cooler, specifically whether the compressor is engaged. The In-Row
Cooler status is on when the compressor is running and is on standby when the compressor is off.
Note: When in standby, the fans may still rotate to help circulate air.
• Language: The language selection for the user interface.