Carrier 39LA-25 Installation, Start-Up And Service Instructions Manual page 24

Indoor air-handling units
Table of Contents

Advertisement

PARAMETER
GROUP NUMBER
34
40
53
98
*
Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v /
60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
† Motor Nameplate Amps. Factory programmed per Programmed Set-
tings in Table 6. This value should always be compared to the actual
motor nameplate value before start-up.
** Maximum Output Amps — Factory programmed per Table 6.
NOTES:
1. All conductors are no. 22 AWG (American Wire Gage) minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, or high pressure switch are not required.
Table 7 — Air Handler VFD Factory-Set Parameters (cont)
NUMBER
3415
3416
3417
3418
3419
3420
3421
4001
4002
4005
4006
4007
4010
4011
4012
4013
4016
4027
5301
5303
5304
5305
5310
5311
9802
Fig. 22 — Field-Supplied Control Wiring for VFD Speed Control
DESCRIPTION
Signal Parameter 3
Signal 3 Minimum
Signal 3 Maximum
Output 3 DSP From
Output 3 DSP units
Output 3 Minimum
Output 3 Maximum
Gain
Integration Time
Error Value Invert
Units
Display Format
Setpoint Select
Internal Setpoint
Setpoint Minimum
Setpoint Maximum
ACT 1 Input
PID Parameter Set
EFB Protocol ID
EFB Baud Rate
EFB Parity
EFB Control Profile
EFB PAR 10
EFM PAR 11
Comm Prot SEL
24
VFD DRIVE ONLY PARAMETERS
Speed
0
30000
0
rpm
0
3000
0.7
30 sec.
no
volts
x.xxx
Internal
Field Program (0.0v~10,0v)
0 v
10.0v
AI-2
SET 1
0
9.6
8 NONE 1
ABB DRV LIM
0
0
NOT SEL