5. Dimensions & safety distances
Warnings
During operation, all metallic parts of the breaker, except control box and
closing solenoid drive, may carry dangerous voltages.
Insulation covers are available as an option.
For installation of the breaker into cubicle, top and side openings shall be
provided, in order to reduce internal pressure rise during clearing short
circuit.
All openings respectively free areas on the top of the cubical shall be not
less than 50%.
26
Design and specifications are subject to change without notice
01/2008