Electrical connection

6.6 Connecting converters

6.6
Connecting converters
NOTICE
Material damage caused by an excessively high supply voltage
Material damage can occur if the supply voltage is too high for the insulation system.
• Observe the values in the following tables.
SIMOTICS machines can be operated with SINAMICS G converters and SINAMICS S converters
(uncontrolled and controlled infeed) when maintaining the permissible peak voltages.
The insulation system of SIMOTICS machines corresponds to the specifications laid down in
IEC 60034-18-41 according to voltage stress category C (IVIC C = high stress).
Table 6- 5
Maximum voltage peaks at the motor terminals for line (DOL) motors, converter operation possible
Rated motor voltage
V
≤ 500 V
Table 6- 6
Maximum voltage peaks at the motor terminals for motors specifically designed for converter operation (e.g.
VSD 10)
Rated motor voltage
V
≤ 500 V
> 500 V to 690 V
Depending on the step height, the voltage rise times for the individual voltage steps in the
line-to-ground voltage at the motor end of the cable must not fall below the following values.
Table 6- 7
Rise times as a function of voltage level
Step height
80
Û
phase-to-phase
V
pk
1500
Û
phase-to-phase
V
pk
1600
2200
V
900
1050
1260
Maximum peak voltage at the motor terminals
Û
phase-to-ground
V
pk
1100
Maximum peak voltage at the motor terminals
Û
phase-to-ground
V
pk
1400
1500
Operating Instructions, 10/2021, A5E41926185A
DC link U
DC link U
1080
Minimum rise time t
r
ns
100
200
400
1MB..5/6 shaft height 71 ... 355
DC
V
750
DC
V
750