Chapter 7 Buffer read/write instructions
- In the following cases, operation error occurs;
a) Special function module is not founded at the slot number specified at 'n1'
b) The value of 'n2' is greater than 512, or [ D + n2 ] is exceeds the range of specified
device.
- Execution conditions
Input condition
GET
GETP
2) Program example
- Program that reads address 14, 15 of buffer memory of the A/D module (G4F-AD3A)
mounted at the slot 3, and stores them to the D0014, D0015 of CPU module.
Input
condition
- Program that reads a ddress 09, 10 of buffer memory of the A/D module (G6F-AD2A) mounted
at the slot 3, and stores them to the D0014, D0015 of CPU module.
Input
condition
Buffer memory
G4F -AD3A
(G6F-AD2A)
of A/D module
12 (07)
13 (08)
14 (09)
15 (10)
16 (11)
Executed per scan
Executed only once
GET
00003 00014 D0014 00002
GET
00003 00009 D0014 00002
2001
2 words
1999
7 - 2
Executed per scan
Executed only once
CPU module
D0012
D0013
2001
D0014
1999
D0015
D0016
2 words