Redirecting The Plume Terminal Discharge - Worcester Greenstar Condensfit II Installation Instructions Manual

Wall mounted gas condensing appliance flue
Hide thumbs Also See for Greenstar Condensfit II:
Table of Contents

Advertisement

Plume management system
▶ Secure the outlet assembly elbow [1]to the extension [4] with the
self-tapping screw [2] provided.
±45°
1
2
4
3
Fig. 45 Fitting the discharge elbow
Under balcony/overhang extension fitting
Refer to figure 46.
▶ Secure the extension [7] to the wall with the support clamp and
screws provided [5].
▶ Remove the screw [1] from the outlet assembly elbow [2] and
remove the grill [3].
▶ Push the outlet assembly elbow [2] fully into the extension tube [7],
the stop tabs set the depth and allow for expansion.
▶ Mark the support for the extension run under the balcony/overhang,
a support clamp is supplied with the extension tube.
The outlet of the extension tube must project at least 100mm past the
balcony/overhang
▶ Drill a hole to suit the wall plug and fit the wall plug.
▶ Screw in the support clamp into the balcony/overhang plug to the
distance shown in figure 46.
▶ Push the extension tube [4] fully into the outlet assembly [2], then
withdraw the tube approximately 10mm to allow for expansion.
▶ Secure the extension [4] to the wall with the support clamp and
screws provided [5].
18
1
4
3
▶ Drill a hole through the plume outlet end secure the grill in place with
the screw [1] removed earlier from the outlet assembly elbow.
1
2
3
2
7
Fig. 46 Fitting extension under balcony/overhang
5.5

Redirecting the plume terminal discharge

The plume deflector can be adjusted to redirect the flue discharge.
NOTICE:
FLUE DISCHARGE
▶ The Plume terminal outlet position must follow the conditions stated
in figure 47. When redirecting the flue discharge the outlet must be at
least 1,500mm from and angle at least 45 ° away from any opening in
the direction of the discharge, as shown. This is to prevent
combustion products from entering the building.
100 mm
1
2
4
5
5
Greenstar Condensfit II – 6 721 819 755 (2019/12)
3