Data traffic
6.3 Acyclic data traffic
6.3.3

Flexible data access: Reading/writing of data sets

With flexible data access, the read and write accesses defined for Modbus are mapped in data
sets DS47, DS48, and DS207, and transferred via PROFINET IO.
Due to transmission of the DS47 (Read DS request) or DS207 (Read logbook request) by the
PROFINET IO controller, the SPP2000 is requested to read and provide the requested data
from the lower-level SENTRON device.
When DS48 (Write DS request) is transferred by the PROFINET IO controller, the SPP2000 is
requested to write the transferred values to the SENTRON device.
Procedure
Figure 6-1
The controller indexes the data with the Write DS47/48 or DS207 request. During this
procedure, the list of data points to be read/written is written to the SPP2000 (=indexed). The
data set may have a maximum length of 240 bytes. The addressing of the data set is
performed via the slot/subslot address of each PAC device.
All new, flexible read requests (Read DS) of other controllers are rejected with the error code
0xB5 (not indexed).
All following Read DS requests of this controller and the new indexing attempts of all other
controllers are rejected with the error code 0xC2 (Busy) until the requested data from
SPP2000 have been provided and the original controller has fetched the requested data.
The following chapters show the data structures of all data sets for read and write accesses
for the SENTRON devices.
You can find the register addresses and data formats in the manuals for the 7KM PAC
46
Example: Reading DS47
PROFINET Proxy SPP2000
Equipment Manual, 03/2022, L1V30814715D-01