6-3. Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the d isplay of the remote
control and the unit op erates as follows.
(1) Automatic operation
The indoor unit operates in according to the
·
current operation.
(2) Cooling operation
The setting temperature drops 3
•
(The value of the setting temperature on the
remote control does not change.)
If the room temperature is higher than the
•
setting temperature by 3.5
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1
°
temperature the horizontal louver returns
automatically.
FAN speed : [AUTO]
•
If the room temperature is higher than the
setting temperature by 3.5
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5
conditioner operates at normal airflow level.
FAN speed : One of 5 levels
•
If the room temperature is higher than the
setting temperature by 3.5
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5
the air conditioner operates at normal airflow
level.
(3) The Hi POWER mode can not be set in Dry of fan
only operation.
C.
°
C or more, the
°
C less than the setting
C or more, the air
°
C, the air
°
C or more, the air
°
6-4. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig.
13UK Series
Heat exchanger
temperature
(°C)
6
2
10UK Series
Heat exchanger
temperature
(°C)
7
5
C,
°
- 10 -
FILE NO. SVM-05039
-4-1 and
-4-2.
6
6
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 6-4-1
Compressor
Outdoor fan
ON
Less than 5°C continues
for 5 minutes
OFF
Fig. 6-4-2