INSTALLER MANUAL VB0171 NOVO+ 100H . 1601717) PART NO VB0172 NOVO+ 200H . 1601719) PART NO ® ENERGY STAR HESE PRODUCTS EARNED THE BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY US EPA. T ENERGY STAR ATURAL ESOURCES ANADA AND THE...
Page 2
ABOUT THIS MANUAL Please take note that this manual uses the following symbols to emphasize particular information: WARNING Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death. CAUTION Denotes an instruction which, if not followed, may severely damage the unit and/or its components. NOTE: Indicates supplementary information needed to fully complete an instruction.
On high speed, the NOVO+ 100H units produce about 150 cfm, and NOVO+ 200H units produce about 192 cfm. According to the Novoclimat Ventilation needs vs. the number of rooms chart, the NOVO+ 100H units can be installed in house having up to 13 rooms*, and NOVO+ 200H can be installed in house having up to 16 rooms*.
4. INSTALLATION WARNING When applicable local regulations comprise more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses. WARNING When performing installation, servicing or cleaning the unit, it is recommended to wear safety glasses and gloves. 4.1 I NSPECT THE ONTENT OF THE...
4. INSTALLATION ( ’ CONT 4.4 C ALCULATING THE Use the table below to ensure that the ducts you intend to install will be carrying air flows at or under the recommended values. Avoid installing ducts that will have to carry air flows near the maximum values and never install a duct if its air flow exceeds the maximum value.
4. INSTALLATION ( ’ CONT 4.5 I NSTALLING THE UCTWORK AND THE EGISTERS WARNING Never install a stale air exhaust register in a room where there is a combustion device, such as a gas furnace, a gas water heater or a fireplace. CAUTION The ductwork is intended to be installed in compliance with all local and national codes that are applicable.
4. INSTALLATION ( ’ CONT 4.6 C ONNECTING THE DUCTS TO THE NSULATED FLEXIBLE DUCTS NOTE: When using flexible ducts, the complete duct run must be accessible and kept as short as possible. Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to outside and fresh air from outside).
4. INSTALLATION ( ’ CONT 4.7 I NSTALLING THE XTERIOR OODS Choose an appropriate location for installing the exterior 6” ø hoods: XHAUST (152 • At a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination NTAKE •...
5. CONTROLS 5.1 I NTEGRATED ONTROL All units are equipped with an integrated control, located in front of the electrical compartment. Use the push button (1) to control the unit. The LED (2) will then show on which mode the unit is in. NOTES: 1.
5. CONTROLS ( ’ CONT 5.2 E ’ LECTRICAL ONNECTION TO PTIONAL ONTROL CONT Use the terminal connector included in the installation kit to perform the electrical connection for main and auxiliary wall controls. Check if all wires are correctly inserted in their corresponding holes in the terminal block.
6. ELECTRIC CONNECTION TO THE FURNACE WARNING Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control. OR A FURNACE CONNECTED TO A COOLING SYSTEM On some older thermostats, energizing the “R”...
7. WIRING DIAGRAM WARNING • Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source. • This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation. If the fuse blows, unplug the product and check the polarity and voltage output from the outlet.
8. BALANCING THE UNIT 8.1 W HAT YOU EED TO ALANCE THE • A magnehelic gauge capable of measuring 0 to 0.5 inch of water (0 to 125 Pa) and 2 plastic tubes. • The balancing chart of the unit. VP0009 8.2 P RELIMINARY...
9. OVERALL VERIFICATION 9.1 O PTIONAL ONTROLS This procedure allows the installer to verify that all modes of operation are fully functional. During the verification of a main control, make sure that all optional remote controls are inactive. LATINUM At its very start-up, the Platinum wall control will perform a booting sequence before being ready to operate. The booting sequence is done when the hour display is flashing.
10. MAINTENANCE / INSTRUCTIONS FOR USER WARNING Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source. • Review with the user the steps required for the regular maintenance of her/his ventilation system. These steps are described in detail in the user manual.
11. SERVICE PARTS VL0050 NOVO+ 100H NOVO+ 200H ESCRIPTION . 1601717 . 1601719 ART NO ART NO Hinge assembly kit 13036 13036 Damper supply port assembly 17245 17245 Damper system actuator (including no. 4) 17235 17235 Thermistor kit 17242 17242 Capacitor 7.5 μF...
12. TROUBLESHOOTING If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the list below to know where on the unit the problem occurs. LED flashes GREEN (double blink). • Thermistor error. Replace the thermistor kit.
Page 20
12. TROUBLESHOOTING ( ’ CONT ROBLEMS OSSIBLE CAUSES OU SHOULD TRY THIS 7. The wall control does • The wires may be in reverse position. • Ensure that the color coded wires have been connected to their appropriate not work OR its indicator places.