Application:
Description:
Digital Inputs:
Analog Inputs:
Setpoints:
None
Application File:
Range
Controller
DC2500-EB-200R-200-00000-00-0
Model
Algorithm:
CTRALG
TIMER
Output:
OUTALG
Input 1:
IN1TYP
IN1 HI
IN1 LO
Input 2:
IN2TYP
Control:
LSP'S
SP TRK
PWR UP
SP Hi
SP Lo
ACTION
HYST
Options:
AUXOUT
DIGIN1
APPLICATION NOTE
Feed Pump
Monitor digital inputs to start and stop boiler feedwater and to alarm an open circuit on
high water condition.
Digital Outputs:
None
Analog Outputs:
Level Transmitter
(4-20 mA)
pump01.nge
0–100%
ONOFF
DIS
RLY
4–20
100
0
DIS
1 ONLY
NONE
ALSP
100
0
REV
0
DIS
NONE
S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
Start-Stop relay (ON when Start boiler in
ON, OFF otherwise)
High Water Alarm (ON when high water
alarm input is ON, OFF when high water
alarm input is OFF)
None
DIGIN2
Communications:
ComADR
ComSTA
BAUD
TX_DLY
WS FLT
SDENAB
UNITS
Alarms:
A1S1TY
A1S1VA
A1S1HL
A1S2TY
A2S1TY
A2S1VA
A2S1HL
A2S2TY
ALHYST
ALARM1
BLOCK
DIA AL
Display:
DECMAL
TUNITS
69
NONE
40
MODB
19.2K
1
FP B
DIS
ENG
PROC
75
HIGH
NONE
NONE
NONE
NONE
NONE
50
NoLATCH
DIS
DIS
ONE
NONE
65-0321—01