Voyager Commercial 27½ to 50 Tons CV and VAV

Configuration Input

Note: The unit is hard wired with specific inputs as indicated below. These inputs cause the unit
Where "GND" is indicated below, the input is connected to chassis ground. Where "JUMPER" is
indicated below, both connection points are shown.
Unit Type
V3
V2, Precedent
Non Heat Pump
Cond Fan Cycling
27.5-30 Ton
SA Tempering
(CV Units Only)
Enabled
Disabled
Electric Heat
Heat
No Heat
3 Compressor
27.5-35 Ton
40-50 Ton
Lead/Lag
Disabled
Enabled
Modulating Gas RTOM J3-3
No Modulating Gas Open
Modulating Gas
High Heat (2 Heat
Exchangers)
High Heat
148
to respond with the appropriate outputs. Configuration inputs are only recognized at unit
power-up.
RTOM
RTRM
J3-5
J1-3,J1-5
GND
Open
Jumper
RTOM J3-4
GND
35 Ton
Open
40 Ton
GND
50 Ton
Open
RTOM
J3-1,J3-2
Open
Jumper
RTRM J2-1,J2-2
Open
Jumper
RTRM J3-7
Open
GND
RTRM J3-8
GND
Open
Ground
IGN #2 J1-5
Ground
RT-SVD03G-EN