Final Checks (With Burner Operating) - Riello ENNE/EMME 1400 Manual

Dual fuel heavy oil/ gas burners
Hide thumbs Also See for ENNE/EMME 1400:
Table of Contents

Advertisement

6.11

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the knob of the gas maximum pressure switch to the
minimum end of scale position
 Turn the air pressure switch knob to the maximum end of
scale position
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Darken the flame sensor
Make sure that the mechanical locking systems
on the adjustment devices are fully tightened.
ATTENTION
20176605
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to
ignition failure
36
GB
Tab. K