Troubleshooting - Honeywell DS05 Manual

Dial set pressure regulating valves
Table of Contents

Advertisement

DS05 DIAL SET PRESSURE REGULATING VALVE

TROUBLESHOOTING

Table 2 provides a troubleshooting guide for the DS05 Dial Set Pressure Regulating Valve.
Table 2. Troubleshooting the DS05 Dial Set Pressure Regulating Valve.
Problem
Whistling noise.
Will not hold pressure.
Chatters.
Freezes up.
Pressure gauge measures a lower
pressure under flow conditions than
was originally set during static
conditions.
62-3041—2
• Slightly increase or decrease the outlet pressure until the noise disappears.
• Clean the filter cartridge as described in the Installation section.
• Replace the screen and O-rings.
• Replace the cartridge as shown in Fig. 3.
• Replace bonnet or cartridge if damaged.
• To avoid future freeze-up:
— Temporarily (slightly) open a downstream faucet if the DS05 will be exposed
to temperatures below 32°F (0°C). The slight water flow will eliminate
freeze-up.
— Move the DS05 to a location with an ambient temperature above 32°F (0°C)
If it is currently exposed to prolonged temperatures below 32°F (0°C).
• DS05 is functioning properly. No action is necessary. The pressure decrease is
characteristic of all direct acting pressure regulating valves and is referred to as
falloff.