Dimensional Data
Height
Width
Depth
Unit Weight
Unit Protection Rating
Cooling Data
Refrigerant
Refrigerant Charge
Cooling Capacity at 95 F Enclosure 95 F
Ambient (BTU/Hr.)
Cooling Capacity at Max Conditions
(BTU/Hr.)
Maximum Ambient Temp
Minimum Ambient Temp
Enclosure Airflow
External Airflow
Condensate Management
Heating Data
Capacity
Electrical Data
Rated Voltage (50/60 Hz)
Rated Frequency
Voltage Range
Cooling Amps at Max Conditions
Heating Amps
Compressor RLA / LRA
Evaporator Fan RLA
Condenser Fan RLA
- 36 -

6000 BTU/HR. UNIT CHARACTERISTICS

N360616GXXX
100 lbs / 45 kg
20 oz.
5654/5104
5639/6217
115 V
8.6/9.4
12.2
5.5/39.2
.78/.93
.78/.93
© 2022 nVent
Model
N360626GXXX
36" / 914.4 mm
11.5" / 292.1 mm
14" / 355.6 mm
100 lbs / 45 kg
Type 12/4/4X/3R
R134a
22 oz.
5613/5647
5771/6410
131 F / 55 C
-40 F / -40 C
250/261 CFM
338/365 CFM
Hose discharge / Optional powered C/E
1300 W
230 V
50 / 60 Hz
+/- 10% of rated
4.7/5.0
6.2
2.4/23.0
.39/.53
.39/.53
N360646GXXX
104 lbs / 47 kg
16 oz.
5572/6026
5300/6089
400/460 V 3 phase
1.8/2.1
1.9
1.7/8.1
.39/.53
.39/.53
89215758