8000 Btu/Hr. Unit Characteristics - nvent SPECTRACOOL G52 Instruction Manual

Table of Contents

Advertisement

Dimensional Data
Height
Width
Depth
Unit Weight
Unit Protection Rating
Cooling Data
Refrigerant
Refrigerant Charge
Cooling Capacity at 95 F Enclosure
95 F Ambient (BTU/Hr./W)
Cooling Capacity at Max Conditions
(BTU/Hr./W)
Maximum Ambient Temp
Minimum Ambient Temp
Enclosure Airflow
External Airflow
Condensate Management
Heating Data
Capacity
Electrical Data
Rated Voltage (50/60 Hz)
Rated Frequency
Voltage Range
Cooling Amps at Max Conditions
Heating Amps
Compressor RLA / LRA
Evaporator Fan RLA*
Condenser Fan RLA*
- 32 -

8000 BTU/HR. UNIT CHARACTERISTICS

G520816GXXX
© 2022 nVent
Model
52.69" / 1338.4 mm
17.12" / 435 mm
11.66" / 296.1 mm
128 lbs / 58.1 kg
Type 12/4/4X/3R
R134A
20 oz.
6100 / 6800
7600 / 8350
131 F / 55 C
-40 F / -40 C
285 / 310 CFM
650 / 700 CFM
Hose discharge / Optional powered C/E
2000W
115V
50 / 60 Hz
+/- 10% of rated
9.9 / 11.4
17.3
5.4 / 38.0
.5
.5
G520826GXXX
24 oz.
7035 / 7450
8360 / 8800
230/208-230V
5.2 / 6.9-6.6
9.6
3.7 / 19.0
.3
.3
89209668

Hide quick links: