Terminal
70
71
72
73
74
75
Y
#
(*) If "D" type devices are installed (as defined by EN12453), connect in unverified mode, foresee mandatory maintenance at least every six months.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
TABLE "A" - PARAMETERS
Any modification of parameters/logics must be confirmed by pressing S2 > 5s
TRIMMER
Parameter
Automatic
T1
closing time [s]
T2
Work time [s]
INSTALLATION MANUAL
Definition
Common
STOP, PHOT and BAR inputs common
The command stops movement. (N.C.)
STOP
If not used, leave jumper inserted.
PHOTOCELL input (N.C.).
PHOT (*)
Operation according to "PHOTOCELL/PHOTOCELL DURING CLOSING" logic. If not used, leave
jumper inserted.
FAULT 1
Test input for safety devices connected to PHOT.
Safety edge input (N.C.).
If not used, leave jumper inserted
SHYRA AC SL
BAR/8K2
dip
OFF
OFF
OFF
BAR /
BAR CL /
OFF
BAR TEST /
BAR CL TEST /
BAR 8K2 /
ON
BAR CL 8K2
(*)
ON
SHYRA AC BA
BAR/8K2
dip
OFF
OFF
ON
FAULT 2
Test input for safety devices connected to BAR / BAR CL
Antenna input.
ANTENNA
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver.
Metal bodies close to the antenna can interfere with radio reception. If the transmitter's
SHIELD
range is limited, move the antenna to a more suitable position.
+
+
+
min.
max.
default
Waiting time before automatic closing.
0
120
0
NOTE: Set to 0 if not used.
SHYRA AC SL
Sets the motor working time (from 0 to 90s), after which the motors stop.
In the case where electrical limit switches are used, add a few extra seconds after the gate leaf
stopping time.
5
120
50%
SHYRA AC BA
Motor(s) work time set to 15 seconds.
trimmer at minimum: input 60-61 CLOSE.
trimmer at maximum: input 60-61 START.
Description
Safety edge
Safety edge
check
operation
dip
dip
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
Safety edge
check
dip
OFF
NC input, no verification, reversal only when closing, stop
when opening (BAR CL)
ON
NC input, with verification, reversal only when closing,
stop when opening (BAR CL TEST)
OFF
8K2 input, reversal only when closing, stop when opening
(BAR CL 8K2)
Description
NC input, no verification, reversal while
opening and closing (BAR)
NC input, no verification, reversal only
when closing, stop when opening (BAR
CL)
NC input, with verification, reversal
while opening and closing (BAR TEST)
NC input, with verification, reversal only
when closing, stop when opening (BAR
CL TEST)
8K2 input, reversal when opening and
closing (BAR 8K2)
8K2 input, reversal only when closing,
stop when opening (BAR CL 8K2)
SHYRA -
11