Carrier 19XL Start-Up, Operation And Maintenance Instructions Manual page 74

Hermetic centrifugal liquid chillers 50/60 hz with hcfc-22 and hfc-134a
Table of Contents

Advertisement

Table 9 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
L. CHILLER ALERTS
PRIMARY MESSAGE
RECYCLE ALERT
SENSOR FAULT ALERT
SENSOR FAULT ALERT
LOW OIL PRESSURE
ALERT
AUTORESTART PENDING POWER LOSS
AUTORESTART PENDING LOW LINE VOLTAGE
AUTORESTART PENDING HIGH LINE VOLTAGE
SENSOR ALERT
SENSOR ALERT
CONDENSER PRESSURE
ALERT
RECYCLE ALERT
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.
M. SPARE SENSOR ALERT MESSAGES
PRIMARY MESSAGE
SPARE SENSOR ALERT
COMMON CHWS SENSOR
SPARE SENSOR ALERT
COMMON CHWR SENSOR
SPARE SENSOR ALERT
REMOTE RESET SENSOR
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 1
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 2
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 3
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 4
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 5
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 6
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 7
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 8
SPARE SENSOR ALERT
TEMP SENSOR — SPARE 9
NOTE: See Legend on page 68.
with Troubleshooting Guides (cont)
SECONDARY MESSAGE
HIGH AMPS AT SHUTDOWN High Amps at Recycle: Check guide vane
LEAVING COND WATER
TEMP
ENTERING COND WATER
TEMP
CHECK OIL FILTER
HIGH DISCHARGE TEMP
HIGH BEARING
TEMPERATURE
PUMP RELAY ENERGIZED
EXCESSIVE RECYCLE
STARTS
SECONDARY MESSAGE
ALARM MESSAGE/PRIMARY CAUSE
drive.
Sensor Fault: Check leaving condenser
water sensor.
Sensor Fault: Check entering condenser
water sensor.
Low Oil Pressure Alert: Check oil
V
P Power Loss: Check voltage supply.
V
P [VALUE]* exceeded limit of
[LIMIT].* Check voltage supply.
V
P [VALUE]* exceeded limit of
[LIMIT].* Check voltage supply.
CMPD [VALUE]* exceeded limit of
[LIMIT].* Check discharge temperature.
MTRB [VALUE]* exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.
CRP High Condenser Pressure
[LIMIT]*. Pump energized to reduce
pressure.
Excessive recycle starts.
ALARM MESSAGE/PRIMARY CAUSE
Sensor Fault:
Check common CHWS sensor.
Sensor Fault:
Check common CHWR sensor.
Sensor Fault:
Check remote reset temperature sensor.
Sensor Fault:
Check temperature sensor — Spare 1.
Sensor Fault:
Check temperature sensor — Spare 2.
Sensor Fault:
Check temperature sensor — Spare 3.
Sensor Fault:
Check temperature sensor — Spare 4.
Sensor Fault:
Check temperature sensor — Spare 5.
Sensor Fault:
Check temperature sensor — Spare 6.
Sensor Fault:
Check temperature sensor — Spare 7.
Sensor Fault:
Check temperature sensor — Spare 8.
Sensor Fault:
Check temperature sensor — Spare 9.
74
ADDITIONAL CAUSE/REMEDY
Check that guide vanes are closing.
Check motor amps correction cali-
bration is correct. Check actuator for
proper operation.
Check sensor. See sensor test
procedure.
Check oil filter. Check for improper
oil level or temperature.
Check power supply if there are ex-
cessive compressor starts occurring.
Discharge temperature exceeded
the alert threshold. Check entering
condenser water temperature.
Thrust bearing temperature ex-
ceeded the alert threshold. Check
for closed valves, improper oil level
or temperatures.
Check ambient conditions. Check
condenser pressure for accuracy.
The chiller load is too small to keep
the chiller on line and there have
been more than 5 restarts in 4
hours. Increase chiller load, adjust
hot gas bypass, increase RECYCLE
RESTART DELTA T.
ADDITIONAL CAUSE/REMEDY
Check alert temperature set points
on Equipment Service, SERVICE2
LID table. Check sensor for accu-
racy if reading is not accurate.