Carrier 19XL Start-Up, Operation And Maintenance Instructions Manual page 23

Hermetic centrifugal liquid chillers 50/60 hz with hcfc-22 and hfc-134a
Table of Contents

Advertisement

To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight CONFIG.
6. Press SELECT .
DESCRIPTION
RESET TYPE 1
Degrees Reset at 20 mA
RESET TYPE 2
Remote Temp (No Reset)
Remote Temp (Full Reset)
Degrees Reset
RESET TYPE 3
CHW Delta T (No Reset)
CHW Delta T (Full Reset)
Degrees Reset
Select/Enable Reset Type
ECW CONTROL OPTION
Demand Limit At 20 mA
20 mA Demand Limit Option
Auto Restart Option
Remote Contacts Option
Temp Pulldown Deg/Min
Load Pulldown %/Min
Select Ramp Type:
Temp = 0, Load = 1
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
CCN Occupancy Config:
Schedule Number
Broadcast Option
ICE BUILD Option
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
ICE BUILD Recycle Option
NOTE:
= delta degrees.
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight Lead/Lag.
6. Press SELECT .
DESCRIPTION
LEAD/LAG SELECT
DISABLE =0, LEAD =1,
LAG =2, STANDBY =3
Load Balance Option
Common Sensor Option
LAG Percent Capacity
LAG Address
LAG START Timer
LAG STOP Timer
PRESTART FAULT Timer
STANDBY Chiller Option
STANDBY Percent Capacity
STANDBY Address
NOTE: The Lead/Lag Configuration table is available on PSIO Software Version 09 and higher.
Table 2 — LID Screens (cont)
EXAMPLE 5 — CONFIGURATION (CONFIG) DISPLAY SCREEN
CONFIGURABLE RANGE
–30-30 (–17-17)
–40-245 (–40-118)
–40-245 (–40-118)
–30-30 (–17-17)
0-15 (0-8)
0-15 (0-8)
–30-30 (–17-17)
0-3
DISABLE/ENABLE
40-100
DISABLE/ENABLE
DISABLE/ENABLE
DISABLE/ENABLE
2-10
5-20
0/1
0-99
0-60
0-120
3-99
DISABLE/ENABLE
DISABLE/ENABLE
0-2
DISABLE/ENABLE
EXAMPLE 6 — LEAD/LAG CONFIGURATION DISPLAY SCREEN
LEAD/LAG CONFIGURATION SCREEN
CONFIGURABLE RANGE
0-3
DISABLE/ENABLE
DISABLE/ENABLE
25-75
1-236
2-60
2-60
0-30
DISABLE/ENABLE
25-75
1-236
UNITS
REFERENCE POINT NAME
DEG F (DEG C)
deg
DEG F (DEG C)
res
DEG F (DEG C)
res
DEG F (DEG C)
res
DEG F (DEG C)
restd
DEG F (DEG C)
restd
DEG F (DEG C)
deg
res
ecw
%
dem
dem
astart
r
tmp
kw
ramp
ldsgrp
%
ldsdelta
MIN
maxldstm
occpcxxe
occbrcst
ibopt
ibterm
ibrecyc
UNITS
REFERENCE POINT NAME
leadlag
loadbal
commsens
%
lag
per
lag
add
MIN
lagstart
MIN
lagstop
MIN
preflt
stndopt
%
stnd
per
stnd
add
23
DEFAULT VALUE
20ma
10 (6 )
rt1
85 (29)
rt2
65 (18)
rt
10 (6 )
1
10 (6 )
2
0 (0 )
chw
5 (3 )
sel
0
opt
DISABLE
20ma
40
sel
DISABLE
DISABLE
contact
DISABLE
ramp
3
ramp
10
opt
1
0
20
60
3
DISABLE
DISABLE
0
DISABLE
DEFAULT VALUE
0
DISABLE
DISABLE
50
92
10
10
5
DISABLE
50
93

Hide quick links: