No. Error Code
Cooling operation restricted at outdoor temperature below
23
E441
Tcool_low value (default:0°C)
24
E458
Fan speed error
25
E461
Error due to operation failure of inverter compressor
26
E462
System stop due to full current control
27
E463
Over current trip / PFC over current error
28
E464
IPM Over Current(O.C)
29
E465
Comp. Over load error
30
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
31
E467
unconnected wire of compressor
32
E468
Error on current sensor (Short or Open)
33
E469
Error on DC-Link voltage sensor (Short or Open)
34
E470
Outdoor unit EEPROM Read/Write error (Option)
35
E471
Outdoor unit EEPROM Read/Write error (H/W)
36
E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open)
37
E475
Error on inverter fan 2
38
E483
Overvoltage of H/W detect DC link
39
E484
PFC Overload (Over current) Error
40
E485
Error on input current sensor of inverter 1 (Short or Open)
41
E488
Inverter input voltage sensor error
42
E500
IPM over heat error on inverter 1
43
E508
Smart install is not installed
Blockage detected on high pressure pipe during heating
44
E534
operation.
45
E554
Gas leak detected
46
E556
Error due to mismatching capacity of indoor and outdoor unit
47
E557
DPM remote controller option error
48
E563
Error due to mismatching indoor and outdoor unit
49
E590
Inverter EEPROM Checksum error
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 37
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 37
Meaning
Remarks
1. Check the range of temperature limited for cooling
operation
2. Check the outdoor temperature sensor
FAN1 ERROR
-
-
Check OLP sensor
1. Check if the service valve is open
2. Check the state of refrigerant
3. Check if connecting wire and the pipe are OK
4. Check the compressor
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM Data
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA.
FAN2 ERROR
Check AC Power
Check Outdoor Inverter PBA.
Check Outdoor EEPROM PBA
Check Outdoor Inverter PBA
Check Outdoor Inverter PBA.
-
1. Check if the service valve is open
2. Check if there's any blockage on the refrigerant cycle
(indoor unit/outdoor unit)
3. Check the EEV connection and operation
4. Check if connecting wire and the pipe are OK
5. Check the compressor
Check the refrigerant
Check the indoor and outdoor unit capacity
Check the indoor option code
Check the outdoor EEPROM data and indoor option code
-