Quick Reference Terminal Description - Radionics D9000 Series Installation And Troubleshooting Quick Reference

Control/communicator
Table of Contents

Advertisement

Terminal
1, 2
3
4
5 (+)
6 (+)
7 (+)
8 (+)
9
10
11, 13, 14,
16, 17, 19,
20, 22
12, 15, 18,
21
23 (-)
24 (+)
25
26
27
28
29 (-)
30
31
32 (+)
www.PDF-Zoo.com

Quick Reference Terminal Description

Name
CLASS 2
Connect 16.5 VAC, 40 VA transformer for primary power supply.
TRANSFORMER
Supplies up to 1.4A at 10.2 VDC to 13.9 VDC to powered devices. Use terminal 9
+ AUX POWER
for common. Shares circuit breaker with terminal 24 and the Expansion Port (J4).
BATTERY
Connect 12V, 7Ah rechargeable lead acid type battery's negative terminal (-) to
NEGATIVE ONLY
terminal 4.
BATTERY
Connect 12V, 7Ah rechargeable lead acid type battery's positive terminal (+).
POSITIVE ONLY
Supplies up to 2 A at 10.2 VDC to 13.9 VDC for steady or pulsed alarm output.
+ STEADY OR
Use terminal 9 for common. Programmed as Relay A.
PULSED
Shares circuit breaker with terminals 7 and 8.
ALARM POWER
Supplies up to 2 A at 10.2 VDC to 13.9 VDC for steady or pulsed alarm output. Use
terminal 9 for common. Programmed as Relay B.
+ ALTERNATE
Shares circuit breaker with terminals 6 and 8.
ALARM POWER
D136 Plug-in Relay required: Install a D136 in socket K3 for output at terminal 7.
Supplies up to 1.4 Amps at 10.2 VDC to 13.9 VDC. Use terminal 9 for common.
Programmed as Relay C
+ SWITCHED AUX
Continuous output interrupted by RESET SENSORS or alarm verification.
POWER
Shares circuit breaker with terminals 6 and 7.
D136 Plug-in Relay required: Install a D136 in socket K1 for output at terminal 8.
Terminal 9 is common for Auxiliary Power, Steady or Pulsed Alarm Power, Alternate
COMMON
Alarm Power, and Switched Aux Power (terminals 3, 6, 7, and 8).
Connect to earth ground. A cold water pipe or grounding rod is preferred.
Do not connect to telephone or electrical ground.
EARTH GROUND
ON-BOARD
Connect normally open and/or normally closed detection devices to loop wiring.
POINTS
1 k Ω resistor required at end of loop.
(Inputs)
ON-BOARD
POINTS
Loop returns for on-board points.
(Common)
ZONEX
[D9412/D9112 only] Use terminals 23 and 24 to power ZONEX modules such as the
COMMON
D8125 POPEX module, the D8128C OctoPOPIT, and the D8129 OctoRelay. Shares
circuit breaker with terminal 3 and the Expansion Port (J4).
ZONEX POWER+
ZONEX IN 2
[D9412/D9112 only] Connect ZONEX modules for points 129 to 247 and relays
ZONEX OUT 2
65 to 128 to these terminals.
ZONEX IN 1
Connect ZONEX modules for points 9 to 127 and relays 1 to 64 to these terminals.
ZONEX OUT 1
(The D7412/D7212 uses points 9 to 75.)
COMMON
Common terminal for SDI devices
DATA BUS B
Terminals 30 and 31 are a two wire bus that drives the command centers, printer
DATA BUS A
interface, and access control modules.
Power for SDI devices. This separate protected power output for SDI devices is not
POWER +
affected by shorts on any other terminal.
™ The Radionics logo is a registered trademark of Radionics
© 1997 Radionics, Inc., Salinas, CA, USA. All rights reserved.
Radionics, Inc., PO Box 80012, Salinas, California 93901-0012
firealarmresources.com