Rear Panel - Inter-m PB-6207B Operation Manual

Battery charger
Table of Contents

Advertisement

Rear Panel

Rear Panel
1
8
1. AC POWER INPUT TERMINAL
This is the terminal to connect the power cord. The power used is AC 220-240V 50/60Hz.
2. AUXILIARY OUTPUT (AUX) TERMINAL
Auxiliary output (up to 10A) is one terminal connecting devices without AC power input. The output
is protected by a fuse (F401).
3. AUXILIARY OUTPUT (AUX) FUSE
It is the fuse for auxililary output (Aux), and if error occurs in the device, it shuts off the Aux to protect
the device. If you want to replace the fuse, please use the one which rated capacity is same.
4. TEMPERATURE SENSOR TERMINAL
This is the terminal to connect the sensor for detecting the battery temperature.
5. MAIN OUTPUT TERMINAL
6 output terminals for supplying backup power (up to 40A). The outputs are protected by fuses (F201
to F206). The maximum output for each terminal is 40A.
(※ Note: The sum of 6 main output terminals and auxiliary output terminals cannot exceed 120A.)
6. CONTACT OUTPUT TERMINAL
Contacts that accept 1A at 30VDC or 0.5A at 125VAC.
● 3-pole SPDT switch (NC- C -NO):
- AC operation and device state (approximately 5 second delay after AC power failure).
- Battery status.
- Output voltage status.
7. BATTERY CONNECTION TERMINALS
This is the terminal for connecting the battery. Be sure to configure the connection with the battery
fuse breaker before connecting, paying attention to the polarity. (up to 120A).
2
3
6
5
BATTERY CHARGER
9
10
7
4
PB-6207B
7

Advertisement

Table of Contents
loading

Table of Contents