Toshiba MMU-AP0071YHPUL Service Manual page 53

Table of Contents

Advertisement

<RBC-AMS5*E-UL>
The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
Data
00
0024
Return
Procedure
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
and the [
] button at the same time
to display the "Field setting menu".
→ Push and hold the buttons for more than 4
seconds.
3
Push the [
select "4. Monitor function" on the "Field
setting menu" screen, then push the "
Set" [
Set
Push the [
select the code to check data.
4
Push the [
CANCEL] button to return
to the "Field setting menu" screen.
MENU] button
] / [
] button to
F2] button.
F2
] / [
] button to
Indoor unit data
Code
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
Indoor unit heat exchanger (coil)
03
Indoor unit heat exchanger (coil)
04
Indoor unit fan cumulative operating hours
F3
Indoor unit refrigerant leak detection sensor
E2
* Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
0003 : Sensor is detecting refrigerant leak
Outdoor unit data
Code
Outdoor unit heat exchanger (coil)
60
61
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
6A
6D
Compressor cumulative operating hours
F1
- 53 -
Data name
temperature (TCJ)
temperature (TC)
(x1 h)
output*
Data name
temperature (TE)
Outside air temperature (TO)
Heatsink temperature (THS)
Operating current (x1/10)
Outdoor heat exchange (coil)
temperature (TL)
(x100 h)