Elmdene 2401ST Series Manual

Elmdene 2401ST Series Manual

24.0v dc 1 amp switch mode power supply for fire detection, fire alarm, smoke and heat control systems (aov)
Hide thumbs Also See for 2401ST Series:
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Elmdene International Ltd
3 Keel Close, Interchange Park,
Portsmouth, Hampshire, PO3 5QD, UK
for Fire Detection, Fire Alarm, Smoke and Heat Control Systems (AOV)
Thank you for choosing this 2401ST Power Supply. Please read this manual carefully as it provides
information on how to safely install, commission and maintain this equipment.
Page
2
- PSU Specification
3
- Installation (Mains feed, Cable sizing, Mounting enclosures)
4
- Installation cont. (Mains Connection, remote fault signalling, Load connection)
5
- Installation cont. (Battery Charger settings)
6
- Installation cont. (Battery installation, Battery compatibility)
7
- Installation cont. (Battery installation, Final commissioning)
8
- Operating Instructions and Maintenance
9
- Trouble shooting
10
- Developer Section (DUAL-PATH, RS485 communication link)
11
- Disposal and Product Compliance
LED
1
2
3
4
5
6
M A INS FUSE
MAINS
SUPPLY
LOAD OUTPUT
-
-
+
+
L O AD 1
L O AD 2
Technical Support: +44(0)23 9269 6638 (option 3)
24.0V dc 1 Amp Switch Mode Power Supply
EN54-4:1997 +A1 +A2, EN12101-10:2005,
and VdS2541:1996-12 (pending)
2401ST-x
FUSE #1
FUSE #2
+
-
- + -
+
GEN
T
T
FAULT OUTPUTS
2x LOAD
TEMPERATURE SENSOR
OUTPUTS
SERIES BATTERY LINK
+
-
12V
BATTERY
Tel: +44(0)23 9269 6638
Fax: +44(0)23 9266 0483
Web:
EPS
+
-
12V
BATTERY
PAK200790_02A Oct 2019
0333
www.elmdene.co.uk
'x' denotes enclosure size
OUTPUT MONITORING
DUAL-PATH
2x INDIVIDUAL OUTPUT
(DEFAULT)
FAULT OUTPUTS
C OM / NO / NC
©2019 ELMDENE INTERNATIONAL LTD
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 2401ST Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elmdene 2401ST Series

  • Page 1 2x LOAD TEMPERATURE SENSOR OUTPUTS C OM / NO / NC LOAD OUTPUT SERIES BATTERY LINK L O AD 1 L O AD 2 BATTERY BATTERY Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 2: Specification

    This Power Supply Unit (PSU) is only suitable for installation as permanently connected equipment (Power Supply Equipment / PSE). The PSE is NOT SUITABLE for external installation Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 3: Installation

    Knock-outs are provided in the case for mating with external trunking or conduit Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of dust and moisture Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 4 41 for DUAL-PATH monitoring). With the OUTPUT LOAD OUTPUT MONITOR jumper fitted, the outputs are considered as two individual loads. L O AD 1 L O AD 2 Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 5: Standby Current

    250mA load for 24hrs and will be able to deliver 1.35A (ImaxB) for 180s at the end of that period EXAMPLE (b): for EN54 Fire systems, an 2401ST, with 2x 2.1Ah batteries, can support a maximum of 1.0A (ImaxA) load whilst charging the batteries Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 6 RED lead to “Bat+” and the BLACK lead to “Bat–“. BATTERY BATTERY CAUTION: Connect battery leads to PSU terminals FIRST - THEN connect to the battery LAST. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 7 Disconnect one of the battery leads, ensuring that no exposed section of conductor or connector is allowed to contact exposed metal-work, other PSE terminals, or other battery terminals. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 8: Maintenance

    There is no regular maintenance required of the PSE other than periodic testing, and replacement of the standby battery. Reference should be made to the battery manufacturer's documentation to determine typical/expected battery life with a view to periodic replacement of the battery. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 9 High impedance in battery Note LED #4 Flash sequence and refer to Battery fault connection. table YELLOW Ri max 750mΩ Battery internal fault (detected during load test). Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 10 GEN fault relay. This fault should never be seen, but in the extremely rare event that it does, the PSU will operate using default values, but some functions may be compromised, and you are strongly advised to contact Elmdene Technical Support to return the product.
  • Page 11 PSU data, and includes; Mains Voltage; Output1 Voltage/Current; Output2 Voltage/Current; Battery Voltage; Charger Current; GEN Fault condition; EPS Fault condition; Diagnostics fault status (condition 1-6), Battery temperature, Charger status, unit address To enable this feature and obtain the protocol guide, please contact Elmdene Technical Support ISPOSAL OF RODUCT AT ND OF This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and 2013/56/EU (Battery).
  • Page 12: Functional Standards

    Power Supplies intended for use in fire detection and fire alarm systems. Approval Certificates and the Declaration of Performance can be Certification Bodies: AFNOR / CNPP / VdS downloaded from the Elmdene website: https://www.elmdene.co.uk Declaration of Performance: DOP2018-020 DOP2018-021 Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 13 2x LOAD TEMPERATURE SENSOR OUTPUTS C OM / NO / NC LOAD OUTPUT SERIES BATTERY LINK L O AD 1 L O AD 2 BATTERY BATTERY Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 14: Spezifikation

    -20 bis +80 °C (Lagerung) Gehäuseschutzklasse IP30 Dieses Netzteil (PSU) ist nur für die Installation als fest angeschlossenes Gerät (Stromversorgungseinrichtung/PSE) geeignet. Die PSE EIGNET SICH NICHT für die externe Installation. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 15 Zur Passung mit externen Kanälen oder Leitungen sind Ausbrüche vorhanden. Stellen Sie sicher, dass alle nicht verwendeten Löcher (auf der Rückseite des Gehäuses) abgedichtet sind, um das Eindringen von Staub und Feuchtigkeit zu verhindern. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 16 Wenn möglich den Fehler beheben. N/C) N/C) Netzteil Netzausfall (> 8 Sekunden) Netzspannung so schnell wie möglich OM ZU OM ZU abgeschaltet. Standby-Batterie verbraucht. wiederherstellen. EÖFFNET EÖFFNET Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 17 Nicht spezifiziert Nicht spezifiziert 0,10 A (Imax-Standby) NF S 61-940 4 h Standby 0,12 0,22 A 0,67 A Standby-Strom (50 % Leistungsabfall innerhalb von 4 Jahren) Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 18 Kabel die gesamte Verkabelung zwischen den beiden Gehäusen so verlegt werden, dass unter Verwendung geeigneter Kabelverschraubungen von anderen Verkabelungen getrennte Gehäuseein- und -austrittslöcher verwendet werden. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 19 Bitte beachten Sie, dass die Montage dieses Links die - + - Konformität mit den Normen EN54-4, EN12101-10 FAULT OUTPUTS und NF S 61-940 außer Kraft setzt. TEMPERATURE SENSOR Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD SERIES BATTERY LINK...
  • Page 20 Einsetzen oder Herausnehmen des Messgeräts und bei der Wiederherstellung der normalen Batterieverkabelung weiterhin sorgfältig auf alle freiliegende Leiter. Schließen Sie den Deckel und sichern Sie ihn mit den mitgelieferten Befestigungsschrauben. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 21: Wartung

    Außer regelmäßigen Tests und dem Austausch der Standby-Batterie erfordert die PSE keine regelmäßige Wartung. Zur Bestimmung der typischen/erwarteten Batterielaufzeit im Hinblick auf den regelmäßigen Austausch der Batterie ist auf die Dokumentation des Batterieherstellers zu verweisen. Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 22: Fehlerbehebung

    Niedrige Batteriespannung Hohe Impedanz im Blink-Sequenz der LED #4 notieren und Batteriefehler Batterieanschluss. Tabelle beachten. GELB Ri max 750mΩ Batterieinterner Fehler (wird während des Lasttests erkannt). Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 23 Sollte dieser äußerst seltene Fall dennoch eintreten, wird das Netzteil mit Standardwerten betrieben. Einige Funktionen können dabei jedoch beeinträchtigt werden und es wird dringend empfohlen, sich an den technischen Support von Elmdene zu wenden, um das Produkt zurückzugeben. Wenn die Batterie angeschlossen ist, wird die Anzeige eines Kalibrierungsfehlers unterdrückt (aber nicht gelöscht).
  • Page 24 Ausgang1 Spannung/Strom; Ausgang2 Spannung/Strom; Batteriespannung; Strom des Ladegeräts; GEN- Fehlerzustand; EPS-Fehlerzustand; Diagnose-Fehlerstatus (Zustand 1-6), Batterietemperatur, Status des Ladegeräts, Geräteadresse. Um diese Funktion zu aktivieren und den Protokollleitfaden zu erhalten, wenden Sie sich bitte an den technischen Support von Elmdene. NTSORGUNG DES RODUKTS AM EBENSDAUER Dieses Produkt fällt in den Geltungsbereich der EU-Richtlinien 2012/19/EU Waste Electrical and Electronic Equipment (WEEE-Richtlinie über...
  • Page 25 Netzteile für den Einsatz in NF S 61-940:2000 Branderkennungs- und Brandmeldeanlagen. Zulassungszertifikate und die Zertifizierungsstellen: AFNOR/CNPP/VdS Leistungserklärung stehen zum Download auf der Elmdene-Website bereit: Leistungserklärung: DOP2018-008 https://www.elmdene.co.uk DOP2018-009 Technical Support: +44(0)23 9269 6638 (option 3) PAK200790_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...

Table of Contents