Elmdene 2405ST Series Manual

Elmdene 2405ST Series Manual

Switch mode power supply for fire detection, fire alarm, smoke and heat control systems
Hide thumbs Also See for 2405ST Series:

Advertisement

Quick Links

Elmdene International Ltd
3 Keel Close, Interchange Park,
Portsmouth, Hampshire, PO3 5QD, UK
for Fire Detection, Fire Alarm, Smoke and Heat Control Systems (AOV)
Thank you for choosing this 2405ST Power Supply. Please read this manual carefully as it provides
information on how to safely install, commission and maintain this equipment.
Page
2
- PSU Specification
3
- Installation (Mains feed, Cable sizing, Mounting enclosures)
4
- Installation cont. (Mains Connection, remote fault signalling, Load connection)
5
- Installation cont. (Battery Charger settings)
6
- Installation cont. (Battery installation, Battery compatibility)
7
- Installation cont. (Battery installation, Final commissioning)
8
- Operating Instructions and Maintenance
9
- Trouble shooting
10
- Developer Section (DUAL-PATH, RS485 communication link)
11
- Disposal and Product Compliance
LED
1
2
3
4
5
6
MAINS FUSE
MAINS
SUPPLY
LOAD OUTPUT
-
-
+
+
L O AD 1
L O AD 2
Technical Support: +44(0)23 9269 6638 (option 3)
24.0V dc 5 Amp Switch Mode Power Supply
EN54-4:1997 +A1 +A2, EN12101-10:2005,
and VdS2541:1996-12 (pending)
2405ST-x
FUSE #1
FUSE #2
+
-
- + -
+
T T
GEN
EPS
FAULT OUTPUTS
2x LOAD
TEMPERATURE SENSOR
OUTPUTS
SERIES BATTERY LINK
+
-
12V
BATTERY
PAK200789_02A July 2019
Tel: +44(0)23 9269 6638
Fax: +44(0)23 9266 0483
Web:
C HARGER MODE
3
2
1
OUTPUT MONITORING
FAULT OUTPUTS
C OM / NO / NC
+
-
12V
BATTERY
0333
www.elmdene.co.uk
'x' denotes enclosure size
ImaxA
3.0A Total
65Ah
24Ah / 38Ah
4.0A Total
7Ah / 12Ah / 18Ah
5.0A Total
(DEFAULT)
DUAL-PATH
2x INDIVIDUAL OUTPUT (DEFAULT)
©2019 ELMDENE INTERNATIONAL LTD
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 2405ST Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elmdene 2405ST Series

  • Page 1 2x LOAD TEMPERATURE SENSOR OUTPUTS C OM / NO / NC LOAD OUTPUT SERIES BATTERY LINK L O AD 1 L O AD 2 BATTERY BATTERY Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 2: Specification

    This Power Supply Unit (PSU) is only suitable for installation as permanently connected equipment (Power Supply Equipment / PSE). The PSE is NOT SUITABLE for external installation Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 3: Installation

    Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of dust and C and K enclosure E enclosure H enclosure moisture Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 4 43 for DUAL-PATH monitoring). With the OUTPUT OUTPUTS LOAD OUTPUT MONITOR jumper fitted, the outputs are considered as two individual loads. L O AD 1 L O AD 2 Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 5 EXAMPLE (c): for EN54 Fire systems, an 2405ST set to MODE 1, with 2x 18Ah batteries can support a maximum of 5.0A (ImaxA) load whilst charging the batteries Installing the Standby Battery Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 6 It is important that the battery box and the PSU are co-located as shown, and connected using the 3m battery-cable (provided). A fixing bracket is provided to secure the Battery Box to the wall to prevent it moving away from the wall. Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 7 To connect batteries as low as 19V, carefully disconnect one white temperature sensor wire from the “TEMP” terminal block). This will induce a thermistor fault. Then wire the batteries to the terminals Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 8 Continue to observe caution with all exposed conductors when inserting or removing the meter and when restoring normal battery wiring Close cover and secure using fastening screws provided. Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 9: Maintenance

    Battery supporting load. YELLOW PSU off – No power Mains lost / Restore mains, confirm batteries are in (Battery depleted) Battery not supporting load. working condition Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 10 Replace if suspect Flash x5 Fault in output connections to the Dual Path Fault. load Check all cables between PSU and load. (DUAL-PATH mode active only). Flash x6 Technical Support: +44(0)23 9269 6638 (option 3) PAK200789_02A July 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 11 GEN fault relay. This fault should never be seen, but in the extremely rare event that it does, the PSU will operate using default values, but some functions may be compromised, and you are strongly advised to contact Elmdene Technical Support to return the product.
  • Page 12 Power Supplies intended for use in fire detection and fire alarm systems. Approval Certificates and the Declaration of Performance can be Certification Bodies: AFNOR / CNPP / VdS downloaded from the Elmdene website: https://www.elmdene.co.uk Declaration of Performance: DOP2018-026 DOP2018-027 DOP2018-028...

This manual is also suitable for:

2405st-c2405st-k2405st-e2405st-h