Elmdene 2402ST Series Manual

Elmdene 2402ST Series Manual

24.0v dc 2 amp switch mode power supply for fire detection, fire alarm, smoke and heat control systems (aov)

Advertisement

Available languages

Available languages

Elmdene International Ltd
3 Keel Close, Interchange Park,
Portsmouth, Hampshire, PO3 5QD, UK
for Fire Detection, Fire Alarm, Smoke and Heat Control Systems (AOV)
Thank you for choosing this 2402ST Power Supply. Please read this manual carefully as it provides
information on how to safely install, commission and maintain this equipment.
Page
2
- PSU Specification
3
- Installation (Mains feed, Cable sizing, Mounting enclosures)
4
- Installation cont. (Mains Connection, remote fault signalling, Load connection)
5
- Installation cont. (Battery Charger settings)
6
- Installation cont. (Battery installation, Battery compatibility)
7
- Installation cont. (Battery installation, Final commissioning)
8
- Operating Instructions and Maintenance
9
- Trouble shooting
10
- Developer Section (DUAL-PATH, RS485 communication link)
11
- Disposal and Product Compliance
LED
1
2
3
4
5
6
M A INS FUSE
MAINS
SUPPLY
LOAD OUTPUT
-
-
+
+
L O AD 1
L O AD 2
Technical Support: +44(0)23 9269 6638 (option 3)
24.0V dc 2 Amp Switch Mode Power Supply
EN54-4:1997 +A1 +A2, EN12101-10:2005
and VdS2541:1996-12 G220015
2402ST-x
FUSE #1
FUSE #2
+
-
- + -
+
GEN
T
T
FAULT OUTPUTS
2x LOAD
TEMPERATURE SENSOR
OUTPUTS
SERIES BATTERY LINK
+
-
12V
BATTERY
Tel: +44(0)23 9269 6638
Fax: +44(0)23 9266 0483
Web:
EPS
+
-
12V
BATTERY
PAK200788_02A Oct 2019
0333
www.elmdene.co.uk
'x' denotes enclosure size
C HARGER MODE
ImaxA
1.0A Total
24Ah / 38Ah
3
2
12Ah / 18Ah
1.75A Total
7Ah (DEFAULT)
1
2.0A Total
OUTPUT MONITORING
DUAL-PATH
2x INDIVIDUAL OUTPUT
(DEFAULT)
FAULT OUTPUTS
C OM / NO / NC
©2019 ELMDENE INTERNATIONAL LTD
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 2402ST Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Elmdene 2402ST Series

  • Page 1 2x LOAD TEMPERATURE SENSOR OUTPUTS C OM / NO / NC LOAD OUTPUT SERIES BATTERY LINK L O AD 1 L O AD 2 BATTERY BATTERY Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 2: Specification

    This Power Supply Unit (PSU) is only suitable for installation as permanently connected equipment (Power Supply Equipment / PSE). The PSE is NOT SUITABLE for external installation Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 3: Installation

    Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of dust and moisture C and K enclosure E enclosure H enclosure Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 4 41 for DUAL-PATH monitoring). With the OUTPUT LOAD OUTPUT MONITOR jumper fitted, the outputs are considered as two individual loads. L O AD 1 L O AD 2 Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 5 EXAMPLE (c): for EN54 Fire systems, an 2402ST set to MODE 3, with 2x 38Ah batteries can support a maximum of 1.0A (ImaxA) load whilst charging the batteries Installing the Standby Battery Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 6 Connect the two 12 V standby batteries in series using the single link cable provided. Connect the negative of one battery to the positive of the other battery. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 7 Indication: Output 1 = OK Constant Green Indication: Output 2 = OK (See also ‘Status and Fault-Diagnostic LED Indication‘ table for full details of LED indications.) Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 8: Maintenance

    There is no regular maintenance required of the PSE other than periodic testing, and replacement of the standby battery. Reference should be made to the battery manufacturer's documentation to determine typical/expected battery life with a view to periodic replacement of the battery. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 9 High impedance in battery Note LED #4 Flash sequence and refer to Battery fault connection. table YELLOW Ri max 500mΩ Battery internal fault (detected during load test). Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 10 GEN fault relay. This fault should never be seen, but in the extremely rare event that it does, the PSU will operate using default values, but some functions may be compromised, and you are strongly advised to contact Elmdene Technical Support to return the product.
  • Page 11 Battery Voltage; Charger Current; Charger setting; GEN Fault condition; EPS Fault condition; Diagnostics fault status (condition 1-6), Battery temperature, Charger status, unit address To enable this feature and obtain the protocol guide, please contact Elmdene Technical Support ISPOSAL OF RODUCT AT ND OF This product falls within the scope of EU Directives 2012/19/EU Waste Electrical and Electronic Equipment (WEEE) and 2013/56/EU (Battery).
  • Page 12: Functional Standards

    Power Supplies intended for use in fire detection and fire alarm systems. Approval Certificates and the Declaration of Performance can be downloaded from the Elmdene website: https://www.elmdene.co.uk Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 13 2x LOAD TEMPERATURE SENSOR OUTPUTS C OM / NO / NC LOAD OUTPUT SERIES BATTERY LINK L O AD 1 L O AD 2 BATTERY BATTERY Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 14: Spezifikation

    -20 bis +80 °C (Lagerung) Gehäuseschutzklasse IP30 Dieses Netzteil (PSU) ist nur für die Installation als fest angeschlossenes Gerät (Stromversorgungseinrichtung/PSE) geeignet. Die PSE EIGNET SICH NICHT für die externe Installation. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 15 Oberfläche und stellen Sie sicher, dass die Wandbefestigungen geeignet sind, das voll belastete Gewicht zu tragen. Zur Passung mit externen Kanälen oder Leitungen sind Ausbrüche vorhanden. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 16 Anzeige: Ausgang 1 = OK OP2* Konstant grün Anzeige: Ausgang 2 = OK (Für vollständige Details der LED-Anzeigen siehe auch Tabelle „LED-Anzeige für Status und Fehlerdiagnose“.) Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 17 Rot BLINKEND x2 Anzeige: Fehler = fehlende Batterie wird angezeigt (wiederholt) OP1* Konstant grün Anzeige: Ausgang 1 = OK OP2* Konstant grün Anzeige: Ausgang 2 = OK Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 18 BEISPIEL (c): Für EN54 Brandsysteme kann ein auf MODE 3 eingestelltes STV2402 mit 2 x 38- Ah-Batterien maximal 1,0 A (ImaxA) Last beim Laden der Batterien aufnehmen. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 19 STV2402 in C-Box mit 7-Ah- Batterien Batterien Batterien STV2402 in H-Box mit 24-Ah-Batterien STV2402 in H-Box mit 38-Ah-Batterien (Batterie zugunsten der Übersichtlichkeit fehlend) Halterungen montieren Abstandhalter montieren Kompatible Batterien Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 20 Wenn angeschlossen, vergewissern Sie sich, dass der EPS-Fehlerausgang einen geöffneten Kontakt (Com- und N/C-Klemmen = offener Schaltkreis) anzeigt und der GEN-Netzteil-Fehlerausgang einen geschlossenen Kontakt (Com- und N/C-Klemmen = Kurzschluss). Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 21 28 und 29 ein Amperemeter in Reihe mit den Batterieleitungen geschaltet werden. Achten Sie beim Einsetzen oder Herausnehmen des Messgeräts und bei der Wiederherstellung der normalen Batterieverkabelung weiterhin sorgfältig auf alle freiliegende Leiter. Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 22: Wartung

    Legende Frontpanel Anzeige Funktionsstatus Fehler/Standby-(Stütz-)Betrieb/OK Netzstatus Batteriefehler/Volllastladung/Batterie OK Batteriestatus (aufgeladen) Kein(e) Fehler/GEN-(PSU-)Fehler Fehlerstatus Siehe Tabelle unten „LED-Anzeige für Status Diagnosestatus Fehlerdiagnose“) Status OP1 Fehler/OK Status OP2 Fehler/OK Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 23 Ausgangslast trennen und prüfen. Kurzschluss. Blinkend x1 Batterie getrennt Batterieanschlüsse prüfen Keine Batterie Batterie stark entladen Batteriesicherung prüfen. Niedrige Batteriespannung. Niedrige Batteriespannung. Batteriezustand prüfen/Batterie ersetzen. Blinkend x2 Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...
  • Page 24 Sollte dieser äußerst seltene Fall dennoch eintreten, wird das Netzteil mit Standardwerten betrieben. Einige Funktionen können dabei jedoch beeinträchtigt werden und es wird dringend empfohlen, sich an den technischen Support von Elmdene zu wenden, um das Produkt zurückzugeben. Wenn die Batterie angeschlossen ist, wird die Anzeige eines Kalibrierungsfehlers unterdrückt (aber nicht gelöscht).
  • Page 25 Ausgang1 Spannung/Strom; Ausgang2 Spannung/Strom; Batteriespannung; Strom des Ladegeräts; Einstellung des Ladegeräts; GEN-Fehlerzustand; EPS-Fehlerzustand; Diagnose-Fehlerstatus (Zustand 1- 6), Batterietemperatur, Status des Ladegeräts, Geräteadresse. Um diese Funktion zu aktivieren und den Protokollleitfaden zu erhalten, wenden Sie sich bitte an den technischen Support von Elmdene. NTSORGUNG DES RODUKTS AM EBENSDAUER Dieses Produkt fällt in den Geltungsbereich der EU-Richtlinien 2012/19/EU Waste Electrical and Electronic Equipment (WEEE-Richtlinie über...
  • Page 26 3 Keel Close Portsmouth PO35QD 0333-CPR-075603 EN54-4:1997 +A1 +A2 EN12101-10:2005 Netzteile für den Einsatz in Branderkennungs- und Brandmeldeanlagen. Zulassungszertifikate und die Leistungserklärung stehen zum Download auf der Elmdene-Website bereit: https://www.elmdene.co.uk Technical Support: +44(0)23 9269 6638 (option 3) PAK200788_02A Oct 2019 ©2019 ELMDENE INTERNATIONAL LTD...