Application Data - Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet

Combination fire smoke dampers steel 3-v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating
Hide thumbs Also See for Combination Fire Smoke Damper FSD-211:

Advertisement

Application data

damper sleeve dimensional data
The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for
installation of retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be
positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.
LH
Right hand drive is show n
Left hand drive available upon re quest
Actuator Type/Model
ML-4XXX Series Honeywell
MS-4XXX Series Honeywell
MS-4120 Series Honeywell
ML-8XXX Series Honeywell
MS-8XXX Series Honeywell
MS-8120 Series Honeywell
331-4551 Powers
331-2976 Powers
MK2-7121 Invensys
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
3
3
/
in.
4
6 in.
V aries
5
/
3
in.
8
RH
A
5 in.
Sleeve Length
T*
S
B*
RRL, RRL/OCI, or TOR
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
1 in. (25mm)
2 3/8 in. (60mm)
3 3/4 in. (95mm)
1
1
/
in.
2
max.
All Dampers*
When H is 11 in. (279mm) or
less with OCI, RRL, or TOR
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.
Actuators and Accessories
space envelopes
Externally mounted actuators always require space outside
of the damper sleeve. The "S" dimension illustrates the
clearance required for various available actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sleeve. "B" and "T" dimensions are worst case clearance
requirements for some dampers less than 18 in. (457mm)
high. All damper sizes under 18 in. (457mm) high do not
require these worst case clearances. If space availability
above or below the damper sleeve is limited, each damper
size should be individually evaluated.
B*
T*
With
With
RRL, RRL/OCI, or TOR
120 Volt AC
¾ in.(19mm)
3/8 in. (10mm)
3/8 in. (10mm)
24 Volt AC
¾ in.(19mm)
6 in. (152mm)
6 in. (152mm)
Pneumatic (25 psi min.)
6¼ in. (159mm)
12 1/8 in. (308mm)
16½ in. (419mm)
"A" Dimension
in. (mm)
Standard
7 3/16 (183)
12 (305)
S
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6½ in. (165mm)
9¼ in. (235mm)
10 in. (254mm)
Maximum
12 (305)
12 (305)