Download Print this page
Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet
Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet

Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet

Combination fire smoke dampers steel 3-v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating
Hide thumbs Also See for Combination Fire Smoke Damper FSD-211:

Advertisement

Quick Links

APPLICATION
Model FSD-211 is a combination fire smoke damper with 3V style
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire
smoke situations. Model FSD-211 may be installed vertically (with
blades running horizontal) or horizontally and is rated for airflow and
leakage in either direction.
RATINgs
UL 555 Fi re Resistance Rating
Fire Rating:
Dynamic Closure Rating: Actual ratings are size dependent
Maximum Velocity:
Maximum Pressure:
Maximum Temperature: 350ºF (177°C) -- Depending on
UL 555S Leakage Rating
Leakage Class:
Operational Rating:
Maximum Velocity:
Maximum Pressure:
Maximum Temperature: 350ºF (177°C) - Depending on
sTANdARd CONsTRuCTION
Frame:
Blades:
Seals:
Jamb Seals:
Linkage:
Closure Device:
Axles:
Bearings:
sIze LImITATIONs:
Minimum Size:
Maximum Size:

OPTIONAL FeATuRes:

• RRL/OCI (Open closed indication switches)
• Electric or pneumatic actuators
• POC retaining angles
• Smoke detectors
• Momentary switch
• Pneumatic Relief Valve (PRV)
• Security bars
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure
allows damper to perform smoke management functions during a
fire emergency)
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)
RRL's available.
• Sealed transitions and sleeves
Combination
1
Hours
1
2
2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
actuator
I
Actual ratings are actuator dependent
2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
actuator
5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile head
and sill are used on sizes less than
17 in. (432mm) high to maximize free
area and performance.
16 ga. (1.5mm) galvanized steel,
reinforced with 3 longitudinal
structurally designed vee's.
Extruded silicone rubber blade seals
Flexible stainless steel jamb seals
Concealed in jamb.
UL listed 165°F (74°C) RRL
1
in. (13mm) dia. plated steel
2
Bronze sleeve type
8 in. W x 6 in. H (203mm W x 152mm H)
Single Section: 32 in. W x 50 in. H
(813mm W x 1270mm H)
36 in. W x 48 in. H
(914mm x 1219mm)
Multiple Section:
Horizontal: 144 in. W x 96 in. H
(3658mm W x 2438mm H)
Vertical: 128 in. W x 100 in. H
(3251mm W x 2540mm H)
FIRe smOKe dAmPeRs
UL 555 1
Model FSD-211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
"uL CLAssIFIed (see complete marking on
product)"
"uL CLAssIFIed to Canadian safety standards
(see complete marking on product)"
Standard 555 & 555S (Listing #R13317)
R
H*
LH
*W&H dimensions furnished approximately ¼in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
Installation installations available at www.greenheck.com
model Fsd-211
Steel 3-V Blades
UL 555S Leakage Class I
Hour Fire Resistance Rating
1
2
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
W*
RH

Advertisement

loading

Summary of Contents for Greenheck Combination Fire Smoke Damper FSD-211

  • Page 1: Optional Features

    Steel 3-V Blades UL 555S Leakage Class I ⁄ Hour Fire Resistance Rating Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance...
  • Page 2: Pressure Drop Data

    Pressure drop data This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
  • Page 3 0.49 1.16 4000 0.64 Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams.
  • Page 4 0.33 0.63 4000 0.42 Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams.
  • Page 5 1.42 2.17 4000 1.86 Greenheck Fan Corporation certifies that the model FSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams.
  • Page 6: Application Data

    Application data damper sleeve dimensional data The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installation of retaining angles and duct connections.
  • Page 7 These dimensions are furnished approximately (6mm) undersize, except round and oval dimensions which are approximately in. (3mm) undersize. T s = (2)(Sleeve Thickness) 128 in. (2540mm) Copyright ©2006 Greenheck Fan Corporation 96 in. (2435mm 32 in. (813mm) (54mm) FSD-211 Rev 3 June 2006...