AmCA 5.5 Pressure drop
12 in. x 12 in. (305mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.06
1000
0.22
1500
0.50
2000
0.89
2500
1.39
3000
2.00
3500
2.72
4000
3.55
24 in. x 24 in. (610mm x 610mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.03
1000
0.14
1500
0.31
2000
0.54
2500
0.85
3000
1.22
3500
1.66
4000
2.17
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
R
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
36 in. x 36 in. (914mm x 914mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.03
1000
0.12
1500
0.26
2000
0.46
2500
0.73
3000
1.05
3500
1.42
4000
1.86
4 (W) (H)
D
3.14
12 in. x 48 in. (305mm x 1219mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.03
1000
0.13
1500
0.30
2000
0.53
2500
0.83
3000
1.19
3500
1.62
4000
2.11
Fsd-211
48 in. x 12 in. (1219mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.04
1000
0.17
1500
0.38
2000
0.67
2500
1.04
3000
1.50
3500
2.05
4000
2.67