Download Print this page

Greenheck Combination Fire Smoke Damper FSD-211 Specification Sheet page 3

Combination fire smoke dampers steel 3-v blades ul 555s leakage class i ul555 11⁄2 hour fire resistance rating
Hide thumbs Also See for Combination Fire Smoke Damper FSD-211:

Advertisement

AmCA 5.2 Pressure drop
12 in. x 12 in. (305mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.04
1000
0.14
1500
0.31
2000
0.55
2500
0.86
3000
1.24
3500
1.69
4000
2.20
Figure 5.3
Figure 5.2
Figure 5. 5
24 in. x 24 in. (610mm x 610mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.02
1000
0.07
1500
0.16
2000
0.29
2500
0.45
3000
0.65
3500
0.89
4000
1.16
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
R
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
5D
36 in. x 36 in. (914mm x 914mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.04
1500
0.09
2000
0.16
2500
0.25
3000
0.36
3500
0.49
4000
0.64
D =
12 in. x 48 in. (305mm x 1219mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.01
1000
0.06
1500
0.13
2000
0.23
2500
0.36
3000
0.52
3500
0.70
4000
0.92
Fsd-211
4 (W) (H)
3.14
48 in. x 12 in. (1219mm x 305mm)
Pressure Drop
Velocity (fpm)
(in. wg)
500
0.03
1000
0.10
1500
0.23
2000
0.41
2500
0.63
3000
0.91
3500
1.24
4000
1.62

Advertisement