compressor application, all compressor relays and related func-
tions will track with their associated DIP switch 2 on S1.
NIGHT LOW LIMIT (NLL) STAGED HEATING — In
NLL staged Heating mode, the override (OVR) input becomes
active and is recognized as a call for heating and the control
will immediately go into a Heating Stage 1 mode. With an ad-
ditional 30 minutes of NLL demand, the control will go into
Heating Stage 2 mode. With another additional 30 minutes of
NLL demand, the control will go into Heating Stage 3 mode.

Units with HWR Option

FAN ONLY — A (G) call from the thermostat to the (G)
terminal of the Deluxe D control board will bring the unit
on in fan only mode.
COOLING STAGE 1 — A simultaneous call from (G),
(Y1), and (O) to the (G), (Y1), (O/W2) terminals of the Deluxe
D control board will bring the unit on in 1st Stage Cooling.
COOLING STAGE 2 — A simultaneous call from (G),
(Y1), (Y2), and (O) to the (G), (Y1), (Y2), and (O/W2) ter-
minals of the Deluxe D control board will bring the unit on
in Cooling Stage 2. When the call is satisfied at the thermo-
stat the unit will continue to run in Cooling Stage 1 until the
Cooling Stage 1 call is removed or satisfied, shutting down
the unit.
NOTE: Not all units have two-stage cooling functionality.
HEATING STAGE 1 — A simultaneous call from (G) and
(Y1) to the (G) and (Y1) terminals of the Deluxe D control
board will bring the unit on in Heating Stage 1.
HEATING STAGE 2 — A simultaneous call from (G),
(Y1), and (Y2) to the (G), (Y1), and (Y2) terminals of the
Deluxe D control board will bring the unit on in Heating
Stage 2. When the call is satisfied at the thermostat the unit
will continue to run in Heating Stage 1 until the call is
removed or satisfied, shutting down the unit.
NOTE: Not all units have two-stage heating functionality.
REHEAT MODE — A call from the humidistat/dehumid-
istat to the (H) terminal of the Deluxe D control board will
bring the unit on in Reheat Mode if there is no call for cool-
ing at the thermostat. When the humidistat/dehumidistat call
is removed or satisfied the unit will shut down.
NOTE: Cooling always overrides Reheat Mode. In the Cool-
ing mode, the unit cools and dehumidifies. If the cooling
thermostat is satisfied but there is still a call for dehumidifi-
cation, the unit will continue to operate in Reheat Mode.

SYSTEM TEST

System testing provides the ability to check the control
operation. The control enters a 20-minute Test mode by mo-
mentarily shorting the test pins. All time delays are increased
15 times. See Fig. 19-22.
To enter Test mode on Complete C or Deluxe
Test Mode —
D controls, cycle the power 3 times within 60 seconds. The LED
(light-emitting diode) will flash a code representing the last fault
when entering the Test mode. The alarm relay will also power on
and off during Test mode. See Tables 27 and 28. To exit Test
mode, short the terminals for 3 seconds or cycle the power 3
times within 60 seconds.
NOTE: Deluxe D Control has a flashing code and alarm relay
cycling code that will both have the same numerical label.
For example, flashing code 1 will have an alarm relay cycling
code 1. Code 1 indicates the control has not faulted since the
last power off to power on sequence.
In Retry mode, the status LED will start to
Retry Mode —
flash slowly to signal that the control is trying to recover from
an input fault. The control will stage off the outputs and try to
again satisfy the thermostat used to terminal Y. Once the ther-
mostat input calls are satisfied, the control will continue normal
operation.
NOTE: If 3 consecutive faults occur without satisfying the
thermostat input call to terminal Y, the control will go into
lockout mode. The last fault causing the lockout is stored in
memory and can be viewed by entering Test mode.
Table 27 — Complete C Control Current LED
Status and Alarm Relay Operations
LED STATUS
DESCRIPTION OF OPERATION
On
Complete C Control is
Off
Slow Flash
Fast Flash
Slow Flash
Over/Under Voltage Shutdown
Test Mode — No fault in
Flashing Code 1
Test Mode — HP Fault in
Flashing Code 2
Test Mode — LP Fault in
Flashing Code 3
Test Mode — FP1 Fault in
Flashing Code 4
Test Mode — FP2 Fault in
Flashing Code 5
Test Mode — CO Fault in
Flashing Code 6
Test Mode — Over/Under
Flashing Code 7
shutdown in memory
Flashing Code 8
Test Mode — PM in memory
Test Mode — FP1/FP2
Flashing Code 9
Swapped Fault in memory
CO
— Condensate Overflow
FP
— Freeze Protection
HP
— High Pressure
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes every 1 second.
3. EXAMPLE: "Flashing Code 2" is represented by 2 fast flashes followed by
a 10-second pause. This sequence will repeat continually until the fault is
cleared.
Table 28 — Complete C Control LED Code and
Fault Descriptions
LED
CODE
1
No fault in memory
2
High-Pressure Switch
3
Low-Pressure Switch
4
Freeze Protection
Coax — FP1
5
Freeze Protection Air Coil
— FP2
6
Condensate overflow
7 (Autoreset)
Over/Under Voltage
Shutdown
8
PM Warning
9
FP1 and FP2
Thermistors are swapped
CO
— Condensate Overflow
FP
— Freeze Protection
HP
— High Pressure
37
ALARM RELAY
Normal Mode
Normal Mode with
(closed 5 sec.,
PM Warning
Open 25 sec.)
non-functional
Fault Retry
Lockout
(Closed after
15 minutes)
Cycling Code 1
memory
Cycling Code 2
memory
Cycling Code 3
memory
Cycling Code 4
memory
Cycling Code 5
memory
Cycling Code 6
memory
Cycling Code 7
Cycling Code 8
Cycling Code 9
LEGEND
LED — Light-Emitting Diode
LP
— Low Pressure
PM
— Performance Monitor
FAULT
DESCRIPTION
There has been no fault since
the last power-down to power-
up sequence
HP Open Instantly
LP open for 30 continuous
seconds before or during a
call (bypassed for first 60 sec-
onds)
FP1 below Temp limit for 30
continuous seconds
(bypassed for first 60 seconds
of operation)
FP2 below Temp limit for 30
continuous seconds
(bypassed for first 60 seconds
of operation)
Sense overflow (grounded)
for 30
continuous seconds
"R" power supply is <19VAC
or >30VAC
Performance Monitor Warning
has occurred.
FP1 temperature is higher
than FP2 in heating/test
mode, or FP2 temperature is
higher than FP1 in cooling/

test mode.

LEGEND
LED
Light-Emitting Diode
LP
Low Pressure
PM
Performance Monitor
Open
Cycle
Open
Open
Closed
Open