• Airflow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
• Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Application that exceed the above could require a
larger motor. Minimum rated SCFM is 350 per ton.
• High-static airflow requires installation of high kit (HSKT240) or factory-built high-static model.
• Unit factory shipped with the sheave set at 2.5 turns open.
Serie comercial pgb, 50 hz, 7 1/2-, 10-, y 15-ton aire acondicionado tipo paquete a gas/electricidad, capacidad de enfriamiento 90,000 a 180,000 btu/h [26.4 to 52.8 kw], capacidad de calefacción 210,000 a 245,000 btu/h [61.5 to 71.8 kw] (12 pages)