Cpg commercial 15- & 20-ton, three-phase packaged gas/electric units

Advertisement

u
c
nit
learanceS
Maintain an adequate clearance around the unit for safety, service, maintenance, and
proper unit operation. Leave a total clearance of 75" on the main control panel side
of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace.
Leave a clearance of 48" on all other sides of the unit for possible compres-
sor removal or service access, and to ensure proper ventilation and
condenser airflow. Do not install the unit beneath any obstruction.
Install the unit away from all building exhausts to inhibit
Ingestion of exhaust air into the unit's fresh-air intake.
e
e
l
lectrical
ntrance
ocationS
SS-CPG180-240
High-Voltage
Entrance
www.goodmanmfg.com
P
S
roduct
36" minimum
roof overhang
12¹/₈"
3³/₅"
Low-
Voltage
3⁴/₅"
Entrance
PecificationS
13