19MV PIC6 CFGMETER - Config Metering TABLE CONFIGURATION SHEET
DESCRIPTION
Eco EXV Option
Cond Liquid Level Determination
0=Capacity Percent, 1=Setpoint
Liquid level SP-Cap 0%
Liquid level SP-Cap 25%
Liquid level SP-Cap 50%
Liquid level SP- Cap 75%
Liquid level SP- Cap 100%
Low SST Set Point
Eco EXV Option
Eco EXV Active Threshold
Eco Superheat SP
EXCSV Option
EXCSV Activate Threshold
EXCSV Deactivate Threshold
EXCSV Open Time
EXCXV Close Time
EXCSV Open Step
EXCSV Close Step
DESCRIPTION
Cooling ECW Setpoint
Cooling LCW Setpoint
Base Demand Limit
EWT Control Option
RANGE
Disable/Enable
0 to 1
Disable/Enable
Disable/Enable
19MV PIC6 SETPOINT TABLE CONFIGURATION SHEET
RANGE
15 to 120
–12.2 to 48.9
10.0 to 100.0
Disable/Enable
UNITS
NA
%
%
%
%
%
°F
%
^F
%
%
sec
sec
UNITS
°F
°F
%
CL-7
DEFAULT
VALUE
Enable
0
0.5
1.0
1.5
2.0
2.1
34
Enable
0
10
Enable
95
15
60
120
5
5
DEFAULT
VALUE
60
45
100.0
Disable