jcb G20 Operator's Manual page 46

Table of Contents

Advertisement

Icon
v
v
H
Z
H
Z
A
ECM
CAN
39
Fault
Over Speed
Charge Failure
Low Fuel Level
High Fuel Level
Generator Under Voltage
Generator Over Voltage
Generator Under Frequency
Generator Over Frequency
Delayed Over Current
kW Overload
CAN ECU Fault
CAN Data Fail
Emergency Stop
Oil Sender Open Circuit
Coolant Temperature Sender
Open Circuit
9831/0650-3
Description
The engine speed has risen above
the over speed pre alarm setting.
The auxiliary charge alternator
voltage is low as measured from
the W/L terminal.
The level detected by the fuel lev-
el sensor is below the low fuel level
pre-set alarm setting.
The level detected by the fuel level
sensor is above the high fuel level
pre-set alarm setting.
The generator output voltage has
fallen below the pre-set alarm set-
ting. after the Safety On timer has
expired.
The generator output voltage has
risen above the pre-set alarm set-
ting.
The generator output frequency
has fallen below the pre-set alarm
setting after the `Safety On' timer
has expired.
The generator output frequency
has risen above the pre-set alarm
setting.
The measured current has risen
above the configured trip level for a
configured duration.
The measured kW has risen above
the configured trip level for a con-
figured duration.
The engine ECU has detected an
alarm - check engine light Contact
Engine Manufacturer for support.
The module is configured for CAN
operation and does not detect data
on the engine CAN data link.
The emergency stop button has
been depressed. This failsafe (nor-
mally closed to emergency stop)
input and immediately stops the
set should the signal be removed.
The oil pressure sensor has been
detected as being open circuit.
The coolant temperature sensor
has been detected as being open
circuit.
Operation
Instruments
39