Scroll with the UP / DOWN keys to receive the downward hiden records.
The function to select is displayed flashing. Press the ENTER key to select and to get into
the submenu.

Submenu ventilator settings:

Here you find all settings for both fans-outputs "Exhaust fan" and "Intake fan" exhaust fan
on the left and right supply air fan. On AC fans can be loaded max 2200W per output,
depending on the country and plug type, but you can connect a maximum of 3600W total
load. Depending on model you have, there are in the inside of the 16A controller 2 outputs
for EC-fan 0-10V and PWM signal paralel connected to the AC socket.
1. Set temperature
2. Set humidity
3. Fan settings
Scroll with the UP / DOWN keys to display the below information.
1. Fan day
= Ventilation day
2. Fan night = Ventilation night
3. Hysteresis = hysteresis
What is hysteresis? Hysteresis refers to the value between the lowest and the highest
value of the controlling range.
Example: We set the temperature to 25°C with a hysteresis of 2°C. The fan starts from
25°C to controll and reaches the maximum speed + 2°C hysteresis at 27°C. In this 2°C
hysteresis of 25°C to 27°C, the fan speed changes linearly according the temperature
difference.
The function to select is displayed flashing. Press the ENTER key to select them.
Set fan settings
Set exit 1
Set exit 2
Generl settings
= Temperature setting
= Humidity setting
= Ventilator Setting
Set temperature
Set humidity
Fan settings
page 8 of 15