Settings Of Switched Outputs Exit1; Disabled; Output Sensor 1 Heat - G-Systems 16A User Manual

Ventilation controller
Table of Contents

Advertisement

screen part 2.

Settings of switched outputs EXIT1:

In the main menu you find "Set exit 1" = Settings output exit 1. Push the ENTER button to
get one level deeper into the menu. Than push again to "choose function". The following
functions are available:
Ex = disabled
Ex = T1 heat
Ex = T1 cool
Ex = Rh humidify
Ex = Rh dehumidi
Ex = T2 heat
Ex = T2 cool
Ex = timer
Scroll with UP / DOWN buttons to the desired function and confirm with ENTER. If a
function has already been selected, you can use "set value" to change the values. If you
like to switch to another function, select the new function in"Set exit 1". Change the values
or confirm the new function with the SAVE / EXIT button.

Disabled:

This function turns off the output.

Output Sensor 1 heat:

This function is measuring the air temperature and can be to connected a heater. In the
submenu you can make the following settings:
= Output disabled
= Output sensor 1 heat
= Output sensor 1 cool
= Output sensor 1 humidify/moisturise
= Output sensor 1 dehumidify/drying
= Output sensor 2 heat
= Output sensor 2 cool
= Output timer
Choose function
Ex1= disabled
Ex1= S1 heat
Ex1= S1 cool
Ex1= S2 humidify
Ex1= S2 dehumidi
Ex1= S3 heat
Ex1= S3 cool
Ex1= timer
Exit 1
Heat day
Heatnight 24.0C°
Hyst.
Sensor 1
24.0C°
-02.0C°
page 10 of 15