Service Training
Reverse travel
When moving the travel lever to reverse while driving on level ground, the coil of relay (K26:05) is not
supplied with current.
Current flows
• from potential K11,
• via fuse (F26:23),
• through the closed contact (K26:07)
• to the back-up alarm buzzer (H14:11).
The back-up alarm will sound.
Forward tavel
In this position the proximity switch (B14:05) closes.
Current flows
• from potential K11,
• via fuse (F25:05),
• the closed proximity switch (B14:05),
• to the coil of relay (K26:05).
The relay switches over, the current supply for the warning buzzer (H14:11) is interrupted.
Current flows also
• from potential K11,
• via fuse (F26:23),
• to the travel speed range selector (S42:24).
BW 156/177 D-3/PD-3
- G 15 -
BW 178/179 D-3/PD-3