Anti-scale system chemical-free, salt-free scale prevention (25 pages)
Summary of Contents for Watts Lync WQ-UV
Page 1
Disclaimer The information contained in this manual is subject to change without notice from Lync, a division of Watts Water Technologies, Inc. Lync makes no warranty of any kind with respect to this material, including, but not limited to, implied warranties of merchantability and fitness for a particular application.
1. INTRODUCTION 1.1. System Overview Lync WQ-UV is a complete, fully engineered water quality optimization solution that features sediment filtration and UV disinfection. Lync WQ-UV is factory pre-assembled to minimize installation time and labor. Standard components of this system are: •...
Page 4
SMARTSTREAM. WARNING! Lync WQ-UV contains a UV-C emitter (UV lamp). Unintended use of the appliance or damage to the housing may result in the escape of dangerous UV-C radiation. UV-C radiation may, even in little doses, cause harm to the eyes and skin. Appliances that are obviously damaged must not be operated.
Lync WQ-UV SECTION 1: INTRODUCTION 1.2. Specifications WQ-UV Skid WQUV-050-D WQUV-100-D Peak flow rate 50 gpm 100 gpm Number of Lync UV systems (LD050AGAA) Inlet/Outlet 2” SCH80 PVC Flange Number of Lync Cartridge Filter systems UV Transmittance 95 % UVT...
Page 6
Lync WQ-UV SECTION 1: INTRODUCTION Color Touch Screen with multiple languages, intuitive screen navigation, detailed system status messages, System display type maintenance/diagnostic, and dealer programmable with website/contact information/QR codes UV Sensor Display on graphic touch screen, Lamp life monitor auto-reset with new lamp...
Quartz Sleeve O-Ring 3.2. Installation Lync WQ-UV is a complete system with factory pre-assembled plumbing and wiring to minimize installation time and labor. Components are fastened onto a steel skid for safe and easy transportation and installation. 1. Confirm that the system being installed matches the flow rate for the application.
Lync WQ-UV SECTION 3: Operation • DO NOT install the system outdoors. Keep system away from moisture, rain, and direct sunlight. Ambient air temperature must remain below 122°F and relative humidity must remain below 95%. • The system MUST be installed in accordance with all applicable national, state and local codes.
Lync WQ-UV SECTION 3: Operation NOTE: If water hammer is evident, install water hammer arrestors before the system. WARNING! Do not attempt to remove the cartridge filter lid without relieving pressure. To open lid, close shutoff valves before and after filter, press pressure relief button to relieve pressure. Once pressure has been relieved, remove eyebolts and lid.
Lync WQ-UV SECTION 3: Operation • A 1⁄4" FNPT port and pressure gauge has been installed in the filter's lid to indicate working pressure . A second gauge is installed downstream of the filter in the pipe line to indicate pressure differential and help determine when cartridge replacement may be necessary.
Page 12
Lync WQ-UV SECTION 3: Operation 3.6.2. Overview of Screens When the system is first powered up, this screen will appear. Startup Screen When the system is first powered up, this screen will appear. Lamp Warm Up Screen Once Startup Screen system checks are complete, the lamp warm up screen will appear, and automatically complete the lamp warm up sequence.
Page 13
Lync WQ-UV SECTION 3: Operation 4- Set Up Screen Upon touching , the screen allows the user to select a language as well as the bypassing and silencing of alarms. Touching the house icon from any of these sub-screens will return the user to the Home Screen.
Page 14
Lync WQ-UV SECTION 3: Operation 3.6.3. Normal Operation System checks are automatically executed by the controller in the Start Up Screen then the system advances to the Lamp Warm Up Screen. If an abnormal condition exists, a variety of alarms can be displayed.
Page 15
Lync WQ-UV SECTION 3: Operation The Home Screen is the normal operating screen for the system. In this graphic the lamp is operating at full power. If an alarm or warning condition occurs, the system will notify the user from this screen.
Page 16
Lync WQ-UV SECTION 3: Operation The user will be notified if a lamp failure occurs. Upon a lamp failure condition, the alarm relay will energize to close the outlet solenoid valve (optional) on the system and an audible alarm will sound.
Page 17
Lync WQ-UV SECTION 3: Operation Alarm output relay is not bypassed. 3.6.7. Bypassing Alarms-Audible Alarms Touching the speaker icon will bring up a confirmation screen. Touch Yes to mute the audible alarm for 24 hours and return to the Set Up Screen. Touch No to return to the Set Up Screen with the alarm not muted.
Page 18
Lync WQ-UV SECTION 3: Operation Touching the QR Code icons on the Lamp and Sleeve Replacement Screen will enlarge them. If there are no buttons touched over a 30 seconds period the system will go back to the Home Screen. To return from the full screen QR code, touch the screen.
Lync WQ-UV SECTION 3: Operation 3.7. Modbus Communication Remote communication of the Lync UV control system utilizes Modbus over a RS-485 protocol. Connect the RJ45 cable into CAT 5 ethernet connection port at the bottom of Lync UV controller (see section 3.6. to locate the port). In order to connect the control wiring to Building Management System (BAS), use a RJ45 to terminal block adapter and RS-485 wiring.
Page 20
Lync WQ-UV SECTION 3: Operation Address Register Name Parameters Revealed Group 0x0477 MeasuredUvLevelL Measured UV Level Absolute (low word) CLOD Lamp burning Status of Reduced Arc Current (dimming) Lamp Validation Result 0x0479 ControllerStatusInfo0 Lamp Life Status CLOD UV Sensor Status...
Lync WQ-UV SECTION 3: Operation 3.7.3.1. Lamp Type Input Register Address: 0x0374 This register identifies the specific model of UV lamp that has been attached to the controller. This value applies to the last lamp for which the lamp tag was successfully read by the system since power was applied.
Lync WQ-UV SECTION 3: Operation 3.7.3.2. Lamp Rated Operating Time Input Register Address: 0x0375 This register displays the rated operating time of the UV lamp in hours. This value applies to the last lamp for which the lamp tag was successfully read by the system since power was applied.
Lync WQ-UV SECTION 3: Operation 3.7.3.3. Controller Operating Time Input Register Address: 0x0470 : 0x0471 These registers display the cumulative operating time of the controller. The Controller Operating Time is shown in units of 30 minute intervals. Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A •...
Lync WQ-UV SECTION 3: Operation 3.7.3.4. Lamp Operating Time Input Register Address: 0x0472 : 0x0473 These registers display the cumulative time that the lamp has been operating. The value is specified in units of 15 minute intervals. This value applies to the last lamp for which the lamp tag was successfully read by the system since power was applied.
Lync WQ-UV SECTION 3: Operation 3.7.3.5. Lamp Life Remaining Input Register Address: 0x0475 This register displays the number of days of operation that remain for the lamp before it will have been operated for its rated maximum lifetime or longer.
Lync WQ-UV SECTION 3: Operation 3.7.3.6. Measured UV Level, Absolute Input Register Address: 0x0476 : 0x0477 These registers display the measured UV intensity level reported by the external UV sensor. The value is reported in units of 0.01W/m2 The value 4294967295 (0xFFFFFFFF) is reserved to indicate that the UV level has overflowed the measurement range of the sensor device.
Lync WQ-UV SECTION 3: Operation 3.7.3.7. Controller Status Information Group 0 Input Register Address: 0x0479 This register displays various runtime operating parameters of the system. Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A •...
Page 28
Lync WQ-UV SECTION 3: Operation Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A • 1/26/2022 of 38...
Page 29
Lync WQ-UV SECTION 3: Operation Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A • 1/26/2022 of 38...
Lync WQ-UV SECTION 3: Operation 3.7.3.8. Controller Status Information Group 1 Input Register Address: 0x047A This register displays various runtime operating parameters of the system. Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A •...
Page 31
Lync WQ-UV SECTION 3: Operation Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST L- OMM-006_0A • 1/26/2022 of 38...
Lync WQ-UV SECTION 3: Operation 4. Troubleshooting PROBLEM POSSIBLE CAUSE CORRECTIVE ACTIONS Replace lamp Clean or replace quartz sleeve Replace prefilter Low or no UV transmittance into the water Confirm the pretreatment is adequate Bacteria in outlet water Confirm the feed water meets the feed...
Lync WQ-UV SECTION 4: Replacement Part List 5.2. Lync Cartridge Filter Parts Figure 5-2 Lync Cartridge Filter Parts Item Description Part # Pressure relief assembly includes cap, spring and stem 68100621 Lid with brass reinforced gauge port 68100616 O-ring for lid closure, EPDM 68100619 Adapter 2"...
Lync WQ-UV SECTION 4: Replacement Part List 5.3. Lync UV Parts Use only Lync supplied UV lamps and quartz sleeves. Failure to do so may result in system failure and will void all warranty. Figure 5-3 Lync UV Parts Item...
Lync WQ-UV SECTION 5: Maintenance 6. Maintenance Maintenance Practice Frequency Check for system leaks Every month Check the differential pressure* for cartridge replacement Every two weeks UV lamp replacement Every year Quartz sleeve replacement Every three years * Differential pressure is equal to pressure gauge reading at the inlet side of the filter minus pressure gauge reading at the outlet side of the filter.
Lync WQ-UV SECTION 5: Maintenance 6.2. Lync UV Maintenance UV Lamps have a 1 year (9000 Hour) life span under normal operating conditions. Quartz sleeves should be cleaned with vinegar, citric acid, or a lime scale removing chemical annually and replaced no less than once every 3 years. If the quartz sleeve cannot be cleaned, or if it is discolored, is must be replaced.
Lync WQ-UV SECTION 5: Maintenance 9. Fully insert a new quartz sleeve into the reactor chamber and install the O-ring over the quartz sleeve. Press the O-ring down over the quartz sleeve until it is seated in the bevel of the stainless steel reactor chamber's threaded port.