Advertisement

Quick Links

Pioneering for You
Wilo-Stratos PICO
en Installation and operating instructions
·
4249388 • Ed.01/2021-12

Advertisement

Table of Contents
loading

Summary of Contents for Wilo Stratos PICO

  • Page 1 Pioneering for You Wilo-Stratos PICO en Installation and operating instructions · 4249388 • Ed.01/2021-12...
  • Page 3: Table Of Contents

    11.2 Error messages ........................................  22 12 Accessories.................................... 23 12.1 Wilo-Connect module.................................... 23 12.2 Smart Connect Module BT (Bluetooth)................................  24 13 Disposal.................................... 24 13.1 Information on the collection of used electrical and electronic products.................... 24 Installation and operating instructions Wilo-Stratos PICO...
  • Page 4: General Information

    All rights reserved. Subject to change Wilo shall reserve the right to change the listed data without notice and shall not be li- able for technical inaccuracies and/or omissions. The illustrations used may differ from the original and are intended as an example representation of the device.
  • Page 5: Personnel Qualifications

    Optionally, the pump can be set or controlled via an external module (e.g. Bluetooth). The connection is made via a slot (“Wilo-Connectivity Interface”) above the control module. Installation and operating instructions Wilo-Stratos PICO...
  • Page 6: Overview

    0.5 = minimum delivery head in m 6 = maximum delivery head in m at Q = 0 m³/h Installation length: 130 = 130 mm -−- = 180 mm Stainless steel housing Wilo-Smart Connect module BT included in scope of delivery WILO SE 2021-12...
  • Page 7: Technical Data

    ƒ Never operate with phase angle control. ƒ Use authorised Wilo accessories and genuine spare parts only. Intended use also includes observing these instructions and the specifications and markings on the pump. Any use beyond the intended use is considered misuse and will void any warranty claims.
  • Page 8: Installation And Electrical Connection

    ƒ When installing in the feed of open systems, the safety supply must branch off up- stream of the pump (EN 12828). ƒ Complete all soldering and welding work. ƒ Flush the pipeline system. Fig. 2: Installation positions WILO SE 2021-12...
  • Page 9 Re-mount the thermal insulation shell if required. CAUTION! Insufficient heat dissipation and condensate may damage the control module and glandless motor. • Glandless motor (2) not heat insulating. • Leave all condensate drain openings (3) free. Fig. 4: Installing the pump Installation and operating instructions Wilo-Stratos PICO...
  • Page 10: Electrical Connection

    Ensure that the connecting cable does not touch the pipes or the pump. 6.2.2 Connecting the pump Installing the Wilo-Connector ƒ Disconnect the connecting cable from the power supply. ƒ Observe the terminal assignment (PE, N, L). ƒ Connect and install the Wilo-Connector (Fig. 5a to 5e). WILO SE 2021-12...
  • Page 11: Pump Operation

    PE N Fig. 5: Installing the Wilo-Connector Connecting the pump ƒ Earth the pump. ƒ Connect the Wilo-Connector to the control module until it snaps into place (Fig. 5f). ƒ Activate the power supply. Removing the Wilo-Connector ƒ Disconnect the connecting cable from the power supply.
  • Page 12: Initial Commissioning

      Select language +   Set language ✓ After selecting the language, the display changes to the home screen (factory setting = Dynamic Adapt plus) and the pump can be operated via the main menu. WILO SE 2021-12...
  • Page 13 • After completing the process, the pump continues to run in the set regulation mode. • You can already make additional settings at the pump during the process. These settings become active when the process is completed. Installation and operating instructions Wilo-Stratos PICO...
  • Page 14: Home Screen

    Each sub-menu item consists of an icon and a title. ƒ The title names another submenu or a subsequent settings dialogue. Menu selection Possible settings Setpoint Home screen Pump setting Setting assistant No. of radiators 1 ... 15, 20, 30 WILO SE 2021-12...
  • Page 15 Key lock Key lock ON/Cancel Factory setting Factory setting/Cancel External module (see Chapter 12) Maintenance Pump venting Pump venting ON/Stop Manual restart Manual restart ON/Stop Key lock Key lock ON/Cancel Reset energy counter Reset energy counter/Cancel Installation and operating instructions Wilo-Stratos PICO...
  • Page 16: Commissioning

    It is not necessary to know the appropriate regulation mode and the exact delivery head. The pump automatically determines the correct setpoint via the number of radiators or the heated floor area. No. of radiators: Stratos PICO ... 0.5 – 4 m 0.5 – 6 m 0.5 – 8 m Max.
  • Page 17 Recommended for two-pipe heating systems with radiators to reduce the flow noise at thermostatic valves. H min NOTICE Enter the value to be read from the characteristic curve as the setpoint, not the cal- culated value. Constant differential pressure (Δp-c) Installation and operating instructions Wilo-Stratos PICO...
  • Page 18 If pressure-independent thermostatic valves are installed in the system, it is important to maintain a minimum pressure at these valves. The activated mode for pressure-independent valves ensures this minimum pressure even at a low volume flow. The mode can be activated (ON) or deactivated (OFF). Factory setting: pressure-indep. valve OFF WILO SE 2021-12...
  • Page 19: Device Setting

    This does not reset the power consumption meter or contact data stored on the pump. Maintenance Select “Maintenance” in the main menu. Functions and settings that are useful for commissioning or maintenance are available under the “Maintenance” main menu item. Installation and operating instructions Wilo-Stratos PICO...
  • Page 20 In the event of a fault, these contact details also appear on the pump screen at a rate of every 5 seconds. The contact data can only be saved and updated via the “Smart Connect” function in the Wilo-Assistant app on the pump. To establish the connection, the “Wilo-Smart Connect Module BT” (accessory) is required (see Chapter 12.2).
  • Page 21: Shutdown

    ƒ Disconnect the pump from the power supply. ƒ Contact Wilo customer service or a specialist technician. Maintenance No special maintenance is required during operation. ƒ Under the “Maintenance” main menu item, functions are available that are useful for maintenance.
  • Page 22: Error Messages

    E020 Excessive winding Fluid/ambient temperature Check setting and duty temperature too high point E021 Motor overload Deposits in the pump Request customer service E021 Motor overload Fluid viscosity is too high Check conditions of use (e.g. too much glycol) WILO SE 2021-12...
  • Page 23: Accessories

    E036 Module defective Electronic defective Request customer service If the fault cannot be remedied, contact a specialist technician or the Wilo customer service. Accessories Accessories have to be ordered separately. WARNING Danger of injury or material damage from improper use! •...
  • Page 24: Smart Connect Module Bt (Bluetooth)

    When using the Wilo-Smart Connect Module BT, the pump has a Bluetooth interface to connect to mobile end devices such as smartphones and tablets. You can operate and adjust the pump and read out pump data using Wilo-Smart Con- nect in the Wilo-Assistant app.
  • Page 25 Please consult your local municipality, the nearest waste disposal site, or the dealer who sold the product to you for information on proper disposal. See www.wilo‑recycling.com for more information about recycling. Subject to change without prior notice! Installation and operating instructions Wilo-Stratos PICO...
  • Page 26 DECLARATION OF CONFORMITY Stratos PICO 15/…. Stratos PICO 25/…. We, the manufacturer, declare under our sole Stratos PICO 30/…. responsability that these glandless circulating pump types of the series, (The serial number is marked on the product site plate) in their delivered state comply with the following relevant directives and with the relevant national legislation: _ Electrical Equipment (Safety) Regulations (SI 2016 No.
  • Page 27 DECLARATION OF CONFORMITY KONFORMITÄTSERKLÄRUNG Stratos PICO 15/… We, the manufacturer, declare under our sole Stratos PICO 25/… responsibility that these glandless circulating pump types of the series, Stratos PICO 30/… Als Hersteller erklären wir unter unserer alleinigen Verantwortung, dass die Nassläufer-Umwälzpumpen der...
  • Page 28 Stratos PICO 15/… Stratos PICO 25/… Stratos PICO 30/… || 2014/35/EU - || 2014/30/EU - || 2009/125/EC - || 2011/65/EU + 2015/863 - EN 60335–1:2012+A11:2014+A13:2017+A1:2019+A2:2019+A14:2019; WILO SE EN 60335–2–51:2003+A1:2008+A2:2012; EN IEC 61000–6–1:2019; EN IEC 61000–6–2:2019; Group Quality EN IEC 61000–6–3:2021; EN IEC 61000–6–4:2019; EN 16297–1:2012; EN 16297–2:2012; EN IEC 63000:2018;...
  • Page 29 Vi, producenten, erklærer under vores eget ansvar, at disse kirtelfrie Stratos PICO 15/… cirkulationspumpetyper i serien, Stratos PICO 25/… (Serienummeret er markeret på produktpladen) i deres leverede tilstand overholde følgende relevante direktiver og den Stratos PICO 30/… relevante nationale lovgivning: || 2014/35/EU - Lavspændings || 2014/30/EU - Elektromagnetisk Kompatibilitet || 2009/125/EC - Energirelaterede produkter...
  • Page 30 M s, ražot js, ar pilnu atbild bu pazi ojam, ka šie slapj rotora cirkul cijas Stratos PICO 15/… s k u tipi, Stratos PICO 25/… (S rijas numurs ir nor d ts uz izstr d juma pl ksn tes) pieg d t ja valst atbilst š...
  • Page 31 Stratos PICO 15/… Stratos PICO 25/… Stratos PICO 30/… || 2014/35/EU - H || 2014/30/EU - || 2009/125/EC - || 2011/65/EU + 2015/863 - EN 60335–1:2012+A11:2014+A13:2017+A1:2019+A2:2019+A14:2019; WILO SE EN 60335–2–51:2003+A1:2008+A2:2012; EN IEC 61000–6–1:2019; EN IEC 61000–6–2:2019; Group Quality EN IEC 61000–6–3:2021; EN IEC 61000–6–4:2019; EN 16297–1:2012; EN 16297–2:2012; EN IEC 63000:2018;...
  • Page 32 Noi, produc torul, declar m sub responsabilitatea noastr exclusiv c Stratos PICO 15/… aceste tipuri de pompe de recirculare cu rotor umed, din seria Stratos PICO 25/… (Num rul serial este marcat pe pl cuta de identificare a produsului) în starea lor livrat , respect urm toarele directive relevante i legisla ia Stratos PICO 30/…...
  • Page 36 Local contact at www.wilo.com/contact WILO SE Wilopark 1 44263 Dortmund Germany T +49 (0)231 4102-0 F +49 (0)231 4102-7363 wilo@wilo.com Pioneering for You www.wilo.com...

Table of Contents