Product Description; Function; Interfaces; Marking - Pepperl+Fuchs KD0-RSH-1.1E.1 Series Manual

Table of Contents

Advertisement

Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)

Product Description

2
Product Description
2.1

Function

General
This signal conditioner provides the galvanic isolation between field circuits and control
circuits.
The energized to safe (ETS) function is permitted for SIL 3 applications.
For testing of the relays, test terminals can be used. The test mode will be indicated by a LED.
KCD0-RSH-1.1E.1, KFD0-RSH-1.1E.1
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 230 V AC and the 24 V DC control circuit.
The device is mounted on a 35 mm DIN mounting rail according to EN 60715.
HiC5863
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 30 V and the 24 V control circuit.
This device mounts on a HiC termination board.
HiC5863Y1
The device is a relay module that is suitable for safely switching applications of a load circuit.
The device isolates load circuits up to 230 V AC/30 V DC and the 24 V DC control circuit.
This device mounts on a HiC termination board.
2.2

Interfaces

The device has the following interfaces.
Safety-relevant interfaces: input, output (ETS)
The test input may not be used during normal operation. The test input may be used
for test only.
Note
For corresponding connections see datasheet.
2.3

Marking

Pepperl+Fuchs Group
Lilienthalstraße 200, 68307 Mannheim, Germany
Internet: www.pepperl-fuchs.com
KFD0-RSH-1.1E.1, KCD0-RSH-1.1E.1, HiC5863, HiC5863Y1
8
Up to SIL 3