Pepperl+Fuchs KD0-RSH-1.1E.1 Series Manual page 17

Table of Contents

Advertisement

Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Operation
Proof Test Procedure
1.
Disconnect the field circuit.
2.
Check the device as shown in the following tables.
3.
After check reset the device to the necessary settings.
4.
Connect the field circuit again.
5.
Check the correct behavior of the safety loop. Is the configuration correct?
Test No.
Input or Test Input
1
V
= 24 V DC
Test 1
between terminals 10+ and 9-
2
V
= 24 V DC
Test 2
between terminals 11+ and 9-
3
V
= 24 V DC
Test 3
between terminals 12+ and 9-
4
V
= 24 V DC
Test
between terminals 10+, 11+, 12+ and 9-
5
V
= 0 V DC
Test
between terminals 10+, 11+, 12+ and 9-
6
V
= 24 V DC
input
between terminals 7+ and 8- with regular input
polarity
between terminals 7- and 8+ with inverted input
polarity
Table 5.1
Expected test results for the proof test of KFD0-RSH-1.1E.1
Output (mA)
ETS output (terminals 2, 3): shows < 10 
LED TST is flashing
ETS output (terminals 2, 3): shows < 10 
LED TST is flashing
ETS output (terminals 2, 3): shows < 10 
LED TST is flashing
ETS output (terminals 2, 3): shows < 10 
LED TST is flashing
ETS output (terminals 2, 3): OL (overload)
LED TST is off
ETS output (terminals 2, 3): shows < 10 
LED OUT is on
17