Pepperl+Fuchs KD0-RSH-1.1E.1 Series Manual page 19

Table of Contents

Advertisement

Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Operation
Test No.
Input or Test Input
1
V
= 24 V DC
Test
between terminals 3b+ and 3a-
2
V
= 24 V DC
Test
between terminals 4a+, and 3a-
3
V
= 24 V DC
Test
between terminals 4b+ and 3a-
4
V
= 24 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
5
V
= 0 V DC
Test
between terminals 4a+, 3b+, 4b+, and 3a-
6
V
= 24 V DC
input
between terminals 8a+ and 7a- with regular
input polarity
Table 5.4
Expected test results for the proof test of HiC5863Y1
Only if all tests are successfully done, the proof test is successful.
Output (mA)
ETS output (terminals 1a, 5a): shows < 10 
LED TST is flashing
ETS output (terminals 1a, 5a): shows < 10 
LED TST is flashing
ETS output (terminals 1a, 5a): shows < 10 
LED TST is flashing
ETS output (terminals 1a, 5a): shows < 10 
LED TST is flashing
ETS output (terminals 1a, 5a): OL
(overload)
LED TST is off
ETS output (terminals 1a, 5a): shows < 10 
LED OUT is on
19