Functional Safety K*D0-RSH-1.1E.1, HiC5863(Y1)
Planning
3.2

Assumptions

The following assumptions have been made during the FMEDA:
Failure rates are constant, wear is not considered.
Failure rate based on the Siemens standard SN 29500.
The safety-related device is considered to be of type A device with a hardware
fault tolerance of 0.
The device will be used under average industrial ambient conditions comparable
to the classification "stationary mounted" according to MIL-HDBK-217F.
Alternatively, operating stress conditions typical of an industrial field environment similar
to IEC/EN 60654-1 Class C with an average temperature over a long period of time
of 40 ºC may be assumed. For a higher average temperature of 60 ºC, the failure rates
must be multiplied by a factor of 2.5 based on experience. A similar factor must be used
if frequent temperature fluctuations are expected.
The nominal voltage at the digital input is 24 V. Ensure that the nominal voltage
do not exceed 30 V under all operating conditions.
The DO card must be able to supply a signal current of at least 100 mA.
SIL 3 application
To build a SIL safety loop for the defined SIL, it is assumed as an example that this device
uses 10 % of the available budget for PFD
For a SIL 3 application operating in low demand mode the total PFD
of the SIF (Safety Instrumented Function) should be smaller than 10
hence the maximum allowable PFD
For a SIL 3 application operating in high demand mode the total PFH value
of the SIF should be smaller than 10
would then be 10
If the device is used in applications for high demand mode, perform a risk analysis
regarding systematic faults and implement suitable measures to control these systematic
faults. For example, this can be the following measures:
Since the safety loop has a hardware fault tolerance of 0 and it is a type A device,
the SFF must be > 90 % according to table 2 of IEC/EN 61508-2 for a SIL 3 (sub) system.
-8
per hour.
usage of redundant power supplies,
monitoring of input signal, wiring and connections for short circuits and open circuits,
monitoring the output for open circuits.
/PFH.
avg
value would then be 10
avg
-7
per hour, hence the maximum allowable PFH value
value
avg
-3
,
-4
.