Inspection; Installation - Carrier SINGLE PACKAGED ELECTRIC COOLING UNITS 50GS Installation And Operating Instructions Manual

Single packaged electric cooling units
Hide thumbs Also See for SINGLE PACKAGED ELECTRIC COOLING UNITS 50GS:
Table of Contents

Advertisement

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]
NEC. REQUIRED CLEARANCES.
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
UNIT
ELECTRICAL CHARACTERISTICS
50GS018
208/230-1-60
50GS024
208/230-1-60
50GS030
208/230-1-60, 208/230-3-60
50GS036
208/230-1-60, 208/230-3-60, 460-3-60
50GS042
208/230-1-60, 208/230-3-60, 460-3-60
50GX024
208/230-1-60
50GX030
208/230-1-60, 208/230-3-60
50GX036
208/230-1-60, 208/230-3-60, 460-3-60
Accessory lifting kit is only to be used with Small Packaged
units which have a composite base pan with molded rigging
holds.

INSPECTION

Prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any damage, evidence
INCHES [mm]
INCHES [mm]
UNIT WEIGHT
lb.
254
260
258
268
294
270
291
299
Fig. 2— 50GS018-042 and 50GX024-036 Unit Dimensions
REQUIRED CLEARANCE FOR OPERATION AND SERVICING
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
UNIT HEIGHT
IN. (MM)
"A"
kg
115.2
35.02 (889.5)
20.0 (508.0)
117.9
35.02 (889.5)
19.0 (482.6)
117.0
35.02 (889.5)
19.0 (482.6)
121.6
37.02 (940.3)
20.0 (508.0)
133.3
35.02 (889.5)
19.0 (482.6)
122.5
37.02 (940.3)
18.5 (469.9)
132.0
39.02 (991.1)
19.5 (495.3)
135.6
35.02 (889.5)
19.5 (495.3)
of wear, structural deformation, or cracks. Particular attention
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing any kind of wear in these
areas must not be used and should be discarded.

INSTALLATION

1. Position the lifting bracket assembly around the base of the
unit. Leave the top shipping skid on the unit to act as a
spreader bar. Be sure the strap does not twist.
3
INCHES [mm]
CENTER OF GRAVITY
IN. (MM)
X
Y
13.0 (330.2)
15.0 (381.0)
13.0 (330.2)
15.0 (381.0)
14.0 (355.6)
15.0 (381.0)
14.0 (355.6)
13.0 (330.2)
14.0 (355.6)
13.0 (330.2)
14.5 (368.3)
16.0 (406.4)
15.5 (393.7)
17.6 (447.0)
15.25 (387.4)
16.5 (419.1)
C99007
Z