Modicon TSX Micro (Uni-Telway)
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller station number: 2.
Control area/status area: %MW0 / %MW10.
NOTE
1) HMI station needs to be adjusted to 1 ~ 8.
2) PLC station and HMI station can be the same.
3) The internal memory and relative parameters in PLC should be set properly first. Otherwise, it cannot
communicate except %S.
B. Definition of controller Read/Write address
Registers
Register Type
WORD_DEVICE_ Internal
WORD_DEVICE_ System
WORD_DEVICE_ Input
%KWn is "read only".
Contacts
Contact type
BIT_DEVICE_ Internal
BIT_DEVICE_ System
BIT_DEVICE_ Internal1
%Mn: b is Bit address that corresponds to WORD_DEVICE_ Internal (%MWn).
%Mn is PLC internal relay address.
The read/write range of WORD_DEVICE_ Internal / BIT_DEVICE_ Internal depends on PLC used
memory.
Revision January, 2008, Doc. Name: 2007PDD23000007
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Format
%MWn
n: 0 ~ 65534
%SWn
n: 0 ~ 127
%KWn
n: 0 ~ 65534
Format
Word No.
%Mn:b
n:0 ~ 65534
%Sn
-
%Mn
-
Word No.
Bit No.
N/A
N/A
N/A
Bit No.
b:0 ~ 15
n:0 ~ 127
n:0 ~ 65534
Back to Table
Data Size
Word
Word
Word
1-105