Delta Electronics Network Device DOP-A/AE/AS Connection Manual

Hmi connection manual

Advertisement

Quick Links

www.delta.com.tw/industrialautomation
ASIA
Delta Electronics, Inc.
Taoyuan1
31-1, Xingbang Road, Guishan Industrial Zone,
Taoyuan County 33370, Taiwan, R.O.C.
TEL: 886-3-362-6301 / FAX: 886-3-362-7267
Delta Electronics (Jiang Su) Ltd.
Wujiang Plant3
1688 Jiangxing East Road,
Wujiang Economy Development Zone,
Wujiang City, Jiang Su Province,
People's Republic of China (Post code: 215200)
TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290
Delta Electronics (Japan), Inc.
Tokyo Office
Delta Shibadaimon Building, 2-1-14 Shibadaimon,
Minato-Ku, Tokyo, 105-0012, Japan
TEL: 81-3-5733-1111 / FAX: 81-3-5733-1211
Delta Electronics (Korea), Inc.
Donghwa B/D 3F, 235-6, Nonhyun-dong,
Kangnam-gu, Seoul 135-010, Korea
TEL: 82-2-515-5303/5 / FAX: 82-2-515-5302
Delta Electronics (Singapore) Pte. Ltd.
8 Kaki Bukit Road 2, #04-18 Ruby Warehouse Complex,
Singapore 417841
TEL: 65-6747-5155 / FAX: 65-6744-9228
AMERICA
Delta Products Corporation (USA)
Raleigh Office
P.O. Box 12173,5101 Davis Drive,
Research Triangle Park, NC 27709, U.S.A.
TEL: 1-919-767-3813 / FAX: 1-919-767-3939
EUROPE
Deltronics (The Netherlands) B.V.
Eindhoven Office
De Witbogt 15, 5652 AG Eindhoven, The Netherlands
TEL: 31-40-2592850 / FAX: 31-40-2592851
*We reserve the right to change the information in this manual without prior notice
HMI Connection Manual
20080122
Series

Advertisement

loading

Summary of Contents for Delta Electronics Network Device DOP-A/AE/AS

  • Page 1 Delta Electronics, Inc. Taoyuan1 31-1, Xingbang Road, Guishan Industrial Zone, Taoyuan County 33370, Taiwan, R.O.C. TEL: 886-3-362-6301 / FAX: 886-3-362-7267 Delta Electronics (Jiang Su) Ltd. Wujiang Plant3 1688 Jiangxing East Road, Wujiang Economy Development Zone, Wujiang City, Jiang Su Province,...
  • Page 2 Pin Definition of Serial Communication DOP-A Series COM1 COM2 Pin1 NOTE 1) Mode 3 is for RS-485. Pin 2 & 3 are D+ and pin 1 & 4 are D-. 2) Grounding is highly recommended if RS-485 & RS-422 are used for long transmission. 3) DO NOT connect Frame Ground (FGND) to GND.
  • Page 3 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series DOP-AE Series COM1 COM2/COM3 Pin1 COM2 COM3 Pin1 Mode 1 Mode 2 Mode 3 RS-232 RS-422 RS-485 RXD- RXD+ TXD+ TXD- RTS- RTS+ CTS+ CTS- Revision January, 2008, Doc. Name: 2007PDD23000007 Mode RS-232 Mode 4 Mode 5 RS-232x2...
  • Page 4 DOP AS Series COM1/COM3 Pin1 COM2 Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mode 1 RS-232 COM 1 COM 3 Mode 1 RS-422 RXD- RXD+ TXD- TXD+ Mode 2 RS-232x2 Mode 2 RS-485...
  • Page 5: Usb Connection

    Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Cable for Download Download via COM Port RS-232 DOP series HMI 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RTS (7) CTS (8) Download via USB Flash Drive USB Connection 9 pin D-SUB female (RS-232) (3) TXD (2) RXD...
  • Page 6 Supported Controllers and Devices Please refer to the following table for supported controllers and devices provided by DOP series HMI. Brand Delta Controller For Servo/AC drive/Temperature Controller/PLC Delta (984 RTU mode / ASCII mode) Delta DVP PLC MicroLogix PLC Allen Bradley SLC5 PLC Cimon Loader Protocol...
  • Page 7 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Brand FX / FX2N FX3U A Series/J71UC24 Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH CPU Port Mitsubishi Q Series CPU Port Q Series Computer Link FX Series Computer Link J2s Series BY125 CT150 MC700/720 Modbus (Master) --- 984 RTU / ASCII mode Hexadecimal Address (Master) --- RTU / ASCII mode Modbus nW (Master) --- RTU / ASCII mode...
  • Page 8 Delta (Servo/AC Drive/PLC/Temperature) Controller A. HMI factory setting Baud rate: ASCII: 9600, 7, None, 2. RTU: 9600, 8. None, 2. Controller station number: 1. Control area/status area: None. NOTE 1) This driver can support all Delta products, i.e. AC drive, PLC, Servo, Temperature Controller and Modbus standard connection.
  • Page 9 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Register Type Output Registers RW-n Input Registers Output Registers Input Registers NOTE 1) The above addresses of Servo, AC drive, Temperature controller and PLC Module are in hexadecimal format. PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are in decimal format.
  • Page 10 2) PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are in decimal format. 3) Servo Digital Input and Servo Digital Output are only for Servo. Pay close attention to the following important notes: 4) For Delta AC drive: Communication address for HMI read/write address uses hexadecimal format.
  • Page 11 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) Delta Servo RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-422 DOP Series 9 pin D-SUB male (RS-422) RXD+ (2) RXD- (1) TXD+ (3) TXD- (4) RS-485 DOP Series...
  • Page 12 Delta AC drive RS-485 DOP Series 9 pin D-SUB male (RS-485) R XD + ( 2) TXD+ (3) R XD - (1 ) TXD- (4) GN D ( 5) NOTE 1) When connecting to a Delta VFD-M series AC drive, please connect Pin 5 (GND) of the Delta HMI and Pin 2 (GND) of the Delta VFD-M AC drive.
  • Page 13 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Delta DVP PLC A. HMI factory settings Baud rate: 9600, 7, Even, 1. Controller station number: 1. Control area/status area: D0 / D10. B. Definition of controller Read/Write address Registers Register Type X_Data Y_Data M_Data S_Data...
  • Page 14 C. Connections (Connector Pinouts) RS-232 Connection DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-485 Connection DOP Series 9 pin D-SUB male (RS-485) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 8 pin Mini DIN male (RS-232) (5) TXD...
  • Page 15 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series AllenBradley MicroLogix PLC A. HMI factory setting Baud rate: 19200, 8, None, 1. PLC station number: 1. Control area/status area: B3:0/B3:10. B. Definition of controller Read/Write address Registers Register Type Output File Input File Status File Bit File Timer Flag...
  • Page 16 Contacts Contact Type Output Input Status Timer Timer Preset Value Timer Accumulator Value Counter flag Counter Preset Value Counter Accumulator Value Control Control Size of Bit Array Control Reserved Integer Bit No : Low byte stores Bit address. High byte stores file number. Revision January, 2008, Doc.
  • Page 17 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 Connection DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-16 Controller 8 pin Mini DIN male (RS-232) (7) TXD (4) RXD (2) GND (3) RTS (6) CTS Revision January, 2008, Doc.
  • Page 18 AllenBradley SLC5 PLC A. HMI factory setting Baud rate: 19200, 8, None, 1. PLC station number: 1. Control area/status area: B3:0/B3:10. NOTE 1) Error Check uses CRC (Cyclical Redundancy Check). B. Definition of controller Read/Write address Registers Register Type Output File Input File Status File Bit File...
  • Page 19 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Register Type Counter Accumulator Value Control File Control Size of Bit Array Control Reserved File Integer File Bit No : Low byte is not used, so the value is 0. High byte stores file number. Contacts Contact Type Output...
  • Page 20 Contact Type Timer Accumulator Value Counter Flag Counter Preset Value Counter Accumulator Value Control Control Size of Bit Array Control Reserved Integer Bit No : Low byte stores Bit address. High byte stores file number. NOTE 1) Device O and I need to assign Slot No. (s). If not assign Slot No., it will use default setting 0. Revision January, 2008, Doc.
  • Page 21 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 DOP series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-20 Controller 9 pin D-SUB female (RS-232) (3) TXD (2) RXD (5) SG (7) RTS (8) CTS Revision January, 2008, Doc.
  • Page 22 Cimon PLC (Loader Protocol) A. HMI factory setting Baud rate: 38400, 8, None, 1, RS-232. PLC station number: 1. Control area/status area: D00000 / D00010. B. Definition of controller Read/Write address Registers Register Type Input Output General Purpose Relay General Purpose Relay Latch Relay Flags Timer (Set)
  • Page 23 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 DOP series 9 pin D-SUB male (RS-232) RX D (2 ) TXD (3 ) GND (5) NOTE 1) Device S The unit of PLC internal memory is byte and Device S is read by the unit of byte. Therefore, we recommend the user do not use two consecutive devices S as the read addresses or the interference will occur.
  • Page 24 Copley Servo (Stepnet Protocol) A. HMI factory setting Baud rate: 9600, 8, None, 1. PLC station number: 0. Control area/status area: None. B. Definition of controller Read/Write address Registers Register Type RAM memory Flash memory Internal Register Contacts Contact Type BIT_DEVICE_RB BIT_DEVICE_FB BIT_DEVICE_T0...
  • Page 25 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 DOP series 9 pin D-SUB male (RS-232) RX D (2 ) TXD (3 ) GND (5) 1-24 Controller 9 pin D-SUB female (RS-232) RS -232 TxD RS -232 Rx D Signal Gro und Revision January, 2008, Doc.
  • Page 26 Danfoss VLT 2800 (FC Protocol) A. HMI factory setting Baud rate: 9600, 8, Even, 1, RS-485. PLC station number: 1. Control area/status area: None / None. NOTE 1) Delta HMI can be connected to for VLT-2800, 5000, 6000, 7000 controllers. 2) Each data length format of Danfoss AC drive parameter is not fixed, therefore, “Multiple Duplicate”...
  • Page 27: Control Word

    Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Contacts Contact Type Parameter Bit No : Low byte stores Bit address. High byte stores index number. C. Connections (Connector Pinouts) RS-485 DOP Series 9 pin D-SUB male (RS-485) Explanation of Control Word & Status Word Control Word Bit = 0 No Function...
  • Page 28 Status Word Bit = 0 Timer OK Torque OK Voltage OK Temperature OK Not Running Out of Range Local Control Speed ≠ reference No Warning Reserved Reserved Reserved No Fault Coasting VLT not ready Control not ready Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Bit = 1 Above limit...
  • Page 29 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Emerson EC20 Series PLC A. HMI factory setting Baud rate: 19200, 8, Even, 1 (RS-232). PLC station number: 0. Control area/status area: D0 / D10. B. Definition of controller Read/Write address Registers Register Type Data Word Special Data Word Data Word...
  • Page 30 3) Please note that not all of the addresses can be written when reading SM and SD device. We recommend the user not to set all of the addresses as write address except when setting parameters. C. Connections (Connector Pinouts) RS-232 DOP series 9 pin D-SUB male (RS-232)
  • Page 31 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Facon FB Series PLC A. HMI factory settings Baud rate: 9600, 7, Even, 1. Controller Station number: 1. Control area/status area: R0 / R10. B. Definition of controller Read/Write address Registers Register Type Input Relay Output Relay Internal Relay...
  • Page 32 C. Connections (Connector Pinouts) RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-232 Connecting to CB (Communication Board) or CM (Communication Module) FBs Series Port 1 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-232...
  • Page 33 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Festo PLC A. HMI factory settings Baud rate: 9600, 8, None, 1. Controller Station number: 0. (no PLC station number in protocol) Control area/status area: R0 / R10. NOTE 1) Connectable PLC: FEC-FC Model B.
  • Page 34 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections NOTE 1) Communication port of PLC: COM port 2) It needs to use the dedicated cable for FESTO controllers Cable for transferring TTL to RS-232 and it is 6 pin RJ-12 connector at PLC side. 1-33 Revision January, 2008, Doc.
  • Page 35 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series GE Fanuc 90 Series SNP PLC A. HMI factory settings Baud rate: 19200, 8, ODD, 1. Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: %R1 / %R10.
  • Page 36 Contacts Contact Type Format Discrete Inputs Discrete Outputs Discrete Temporaries Discrete Internals %SA Discretes %SAn %SB Discretes %SBn %SC Discretes %SCn %S Discretes %-Sn Genius Global Data C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-422 DOP Series...
  • Page 37 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Hitachi EH Series PLC A. HMI factory settings Baud rate: 19200, 7, EVEN, 1. Controller station number: 0. Control area/status area: WR0 / WR10. B. Definition of controller Read/Write address Registers Register Type External Input WX External Output WY Internal Output WR...
  • Page 38 NOTE 1) Communication Settings: In Hitachi EH series PLC, only port 1 can be used for communication through procedure 2. The user can select procedure type via DIP switch and specific Special Internal Input (WR). In Hitachi EH-150 series PLC, only EH-CPU***A/448/516/548 can use procedure 2. It needs to set the external I/O (WX, WY, X, Y) of EH series PLC first or HMI cannot read and write their addresses.
  • Page 39 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series slot 0: X48 slot 1: Y32 slot 2: empty16 Analog Type slot 3: X4W slot 4: Y4W 3) Communication Protocol: External I/O (X, Y, WX, WY) Address rules:[r][u][s][n/b]. Word no/Bit no [n/b] Slot number [s] iii) Unit number [u] Remote number [r]...
  • Page 40 HUST CNC Controller A. HMI factory settings Baud rate: 9600, 7, EVEN, 2. Controller station number: 0. Control area/status area: W0 / W10. B. Definition of controller Read/Write address Registers Register Type Format Word Register Double Word Register Dn NOTE 1) The unit for Hust CNC controller is D Word and Wn is the low word of Dn.
  • Page 41 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Jetter Nano Series PLC A. HMI factory settings Baud rate: 9600, 8, EVEN, 1 (RS-232). Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: WR0 / WR10.
  • Page 42 if the read/write address format is set to Rn, only Bit 0 ~ 23 are valid for Rn registers. (Notice: As the Jetter controller is a 24-bit format controller, the valid setting range is 24 Bits. If exceeds this range, HMI will stop read/write operation and show “…..Value is Incorrect” on the screen.
  • Page 43 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Jetter JC Series PLC A. HMI factory settings Baud rate: 9600, 8, EVEN, 1 (RS-232). Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: WR0 / WR10.
  • Page 44 C. Connections (Connector Pinouts) RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 8 pin Mini DIN male (RS-232) (8) TXD (4) RXD (2) GND Controller...
  • Page 45 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Keyence KV/KZ Series A. HMI factory settings Baud rate: 9600, 8, EVEN, 1 (RS-232). Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: DM-0 / DM-10.
  • Page 46 NOTE When using the protocol format of KV series and connecting to KZ-80T PLC, some errors occur. Please refer to the following description: 1) Readable Timer address is not continuous. For example, T-0 ~ T-9 can be read, T10 cannot be read, T11 ~ T20 can be read, T21 ~ T50 cannot be read, …etc.
  • Page 47 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series NOTE 1) Communication Cable: The pins of SD and RD of KZ-80T and KV Series are reverse. 1-46 Revision January, 2008, Doc. Name: 2007PDD23000007...
  • Page 48 Koyo SU/DL Series A. HMI factory settings Baud rate: 9600, 8, ODD, 1 (RS-232). Controller station number: 1. Control area/status area: V1400 / V1410. B. Definition of controller Read/Write address Registers Register Type Timer Accumulated Counter Accumulated V Memory Linker Relays Input Status Output Status Control Relays...
  • Page 49 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD(2) TXD(3) GND(5) 1-48 Controller RJ-11 cable connector (RS-232) (4)TXD (3)RXD (1)GND (6)GND Revision January, 2008, Doc. Name: 2007PDD23000007 Controller RJ-11 cable connector (RS-232) 1 - 6 Top View...
  • Page 50 Koyo K-Sequence A. HMI factory settings Baud rate: 9600, 8, ODD, 1 (RS-232). Controller station number: 1. Control area/status area: R1400 / R1420. NOTE 1) If read / write address exceeds the valid range, HMI will stop read/write operation and show “….Error 6…..
  • Page 51 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Contact type Counter Status Cnnn Spec. Relay 1 SPnnn C. Connections (Connector Pinouts) RS-232 Port 0 Communication Cable 9 pin D-SUB male (RS-232) R XD (2) TX D( 3) GN D( 5) If pin 6 is not grounded, a communication error may occur when connecting to a CKD SM 24R controller. Ensure that pin 6 is well grounded.
  • Page 52 The corresponding registers of CCM2 and K-Sequence Address Corresponding Relationship: CCM2 Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series K sequence SN32DRA 1-51...
  • Page 53 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Lenze LECOM-A/B Protocol A. HMI factory settings Baud rate: 9600, 7, EVEN, 1 (Baudrate: 1200/2400/4800/9600/19200). Controller station number: 1 (1~99). Control area/status area: None / None. NOTE 1) Please pay close attention to each pin definition of cable connectors. 2) Ensure not to use the general RS-232 5-pin cable.
  • Page 54 Register Type Parameter without subcode CDn.m Parameter with subcode CDn/y CDn/y.m NOTE 1) m : HMI communication data format 2) The value of m represents the different communication data format: If m value is undefined: ASCII hexadecimal format (VH). (4 or 8 numbers.) m >= 23 : ASCII hexadecimal format (VH).
  • Page 55 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Only VH type parameter can provide Bit read/write function (it is convenient for the user to read/write Bit No. of parameters). CBn.b, CWn (CWn.m), CDn (CDn.m): read/write address is the same (address n). NOTE 1) Since the data format of this controller is complicated (a.
  • Page 56 00 indicates the global broadcasting number (1~99). 10, 20, 30, 40, 50, 60, 70, 80, 90 are local broadcasting number. The affected ranges are: 11~19, 21~29, 31~39, 41~49, 51~59, 61~69, 71~79, 81~89 and 91~99 respectively. Only choose setting value/setting constant (button), and then the broadcast function can be used.
  • Page 57 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series If the read/write address format is set to CDn, read/write value is the whole Double Word of CDn (1 address). iii) When using character device (e.g. character display, character input…), if the read/write address format is set to CWn, the read/write value is coming from the low word of CWn, CWn+1, CWn+2, …every address.
  • Page 58 LG Master K120S/200S A. HMI factory settings Baud rate: 38400, 8, None, 1. (RS-232) Controller station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: DW0 / DW10. B. Definition of controller Read/Write address Registers Register Type WORD_DEVICE_PW...
  • Page 59 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) NOTE 1) If connecting to Pin 4 (RXD), Pin 7 (TXD) and Pin5 (SG), it indicates that CNet protocol is used (Please refer to the section “LG Master-K simultaneously.
  • Page 60 LG Glofa GM6 CNET A. HMI factory settings Baud rate: 19200, 8, None, 1. (RS-232) Controller station number: 0. Control area/status area: %MW0 / %MW10. NOTE 1) HMI default setting is predefined for CPU Port. If the user want to connect to CNET communication module, the baud rate should be changed to 38400, 8, None, 1.
  • Page 61 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 via CPU Port 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-422 via G6L-CUEC CNET communication module 9 pin D-SUB male (RS-422) 1-60 Controller 9 pin D-SUB male (RS-232) (7) TXD (4) RXD (5) GND...
  • Page 62 LG Master-K CNET A. HMI factory settings Baud rate: 38400, 8, None, 1. (RS-422) Controller station number: 0. Control area/status area: DW0 / DW10. NOTE 1) HMI default setting is predefined for G6L-CUEC CNET communication module. B. Definition of controller Read/Write address Registers Register Type I/O Relay...
  • Page 63 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-422 via G6L-CUEC CNET communication module 9 pin D-SUB male (RS-422) RS-232 via LG-120S PLC (Master K) 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-62 RXD+ (2) RXD- (1) TXD- (4)
  • Page 64 LG XGT CNET A. HMI factory settings Baud rate: 9600, 8, None, 1. Controller station number: 0. Control area/status area: DW0 / DW10. NOTE 1) HMI default setting is predefined for XGL-CH2A CNET communication module. B. Definition of controller Read/Write address Registers Register Type I/O Relay...
  • Page 65 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-422 via XGL-CH2A CNET communication module (Channel 2) 9 pin D-SUB male (RS-422) RS-232 via XGL-CH2A CNET communication module (Channel 1) 9 pin D-SUB male (RS-232) R XD (2) T XD ( 3) G ND (5) 1-64...
  • Page 66 LIYAN LYPLC EX A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller station number: 0. Control area/status area: D0 / D10. B. Definition of controller Read/Write address Registers Register Type Auxiliary Relay Special Auxiliary Relay Status Relay Input Relay Output Relay Timer PV 16-bit Counter PV...
  • Page 67 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-66 Controller 8 pin Mini DIN male (RS-232) (2) TXD (7) RXD (3) GND (6) GND Revision January, 2008, Doc. Name: 2007PDD23000007 Controller 8 pin Mini DIN male (RS-232) Top View...
  • Page 68 M2i Master A. HMI factory settings Baud rate: 38400, 8, None, 1. Controller station number: 1. Control area/status area: SB0 / SB10. B. Definition of controller Read/Write address Registers Register Type Word Address Contacts Contact type Bit Address SBn.b Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Read/Write Range Format...
  • Page 69 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series M2i Slave A. HMI factory settings Baud rate: 38400, 8, None, 1. Controller station number: 1 (no function) Control area/status area: SB0 / SB10. NOTE 1) HMI station number is Slave station number. (default setting is 0) 2) The relation between M2i communication address and HMI internal registers.
  • Page 70 Matsushita FP PLC A. HMI factory settings Baud rate: 9600, 8, ODD, 1. Controller station number: 238. Control area/status area: DT0 / DT10. B. Definition of controller Read/Write address Registers Register Type Internal Relay Special Internal Relay Link Relay External Input Relay External Output Relay Timer/Counter P.V.
  • Page 71 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Increase the range of read / write address (for FP2SH / FP10SH controllers). C. Connections (Connector Pinouts) RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2)
  • Page 72 Mirle FAMA SC A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller station number: 0. Control area/status area: 40100 / 40200. B. Definition of controller Read/Write address Registers Register Type Output Registers Input Registers Input Registers is “read only”. Contacts Contact type Discrete Outputs...
  • Page 73 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi FX/FX2N PLC A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: D0 / D10. NOTE 1) If connecting to Mitsubishi FXxN series PLC, the user can use both FX2N and FX series communication protocol.
  • Page 74 Contacts Contact type Auxiliary Relay Special Auxiliary Relay Status Relay Input Relay Output Relay Timer Flag Counter Flag C. Connections (Connector Pinouts) RS-422 DOP Series 9 pin D-SUB male (RS-422) RXD+ (2) RXD- (1) TXD+ (3) TXD- (4) GND (5) RS-422 9 pin D-SUB male (RS-422) Pi n 2 ( RXD +)
  • Page 75 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi FX3U PLC A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: D0 / D10. B.
  • Page 76 C. Connections (Connector Pinouts) RS-422 DOP Series 9 pin D-SUB male (RS-422) RXD+ (2) RXD- (1) TXD+ (3) TXD- (4) GND (5) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 8pin Mini DIN male (RS-422) (7) TXD+ (4) TXD- (2) RXD+...
  • Page 77 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi A Series AJ71UC24 Communication Module A. HMI factory settings Baud rate: 9600, 8, ODD, 1. Controller Station number: 0. Control area/status area: D0 / D10. NOTE 1) This driver utilizes CheckSum. 2) Please set “PLC Mode” switch to position 5. 3) If OUTPUT Relay (Y) and Special Data Relay (SM) are set to 1, PLC will stop communication and the communication will not recover automatically.
  • Page 78 Contacts Contact type Input Output Link Relay Internal Relay Special Internal Relay Latch Relay Annunciator Timer Contact Timer Coil Counter Contact Counter Coil C. Connections (Connector Pinouts) RS-422 9 pin D-SUB male (RS-422) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Format Word No.
  • Page 79 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH (CPU-S1) CPU Port A. HMI factory settings Baud rate: 9600, 8, ODD, 1. Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: D0 / D10.
  • Page 80 6) Max. read/write registers & relays for communication once 128 Words (256 bytes) Registers 64 Words (128 bytes) Relays B. Definition of controller Read/Write address Registers Register Type Format Input Output Link Relay Internal Relay Special Internal Relay Latch Relay Annunciator Timer Value Counter Value...
  • Page 81 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-422 DOP Series 9 pin D-SUB male (RS-422) Pi n 2 ( RXD +) Pi n 1 ( RXD-) Pi n 4 ( TXD -) Pi n 3 ( TXD +) Pi n 7 ( RT S +) Pi n 8 ( CTS+) Pi n 6 ( RT S -)
  • Page 82 Mitsubishi Q Series CPU Port A. HMI factory settings Baud rate: 19200, 8, ODD, 1. Controller Station number: 0. (no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: D-0 / D-10. NOTE 1) Please notice that no PLC station number in protocol, therefore, only 1(HMI) to 1 (PLC) communication is allowed.
  • Page 83 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Register Type Format File Register ZR-n Link Register Special Link Register SW-n Xn, Yn, DXn, Bn, SBn, Wn, SWn : n is in hexadecimal. Contacts Contact type Input Output Direct input Direct output Latch Relay Annunciator Edge Relay...
  • Page 84 C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 6 pin Mini DIN male (RS-232) (2) SD (TXD) (1) RD (RXD) (3) GND (5) DSR (DR) (6) DTR (ER)
  • Page 85 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi Q Series Computer Link A. HMI factory settings Baud rate: 19200, 8, None, 1. Controller Station number: 0. Control area/status area: D0 / D10. NOTE 1) This communication protocol supports Q series RS232 communication module (QJ71C24-R2) and RS422 communication protocol (QJ71C24N).
  • Page 86 Contact type Link Relay Annunciator Timer Contact Timer Coil Counter Contact Counter Coil Xn, Yn, Bn : n is in hexadecimal. C. Connections (Connector Pinouts) RS-232 DOP Series 9 pin D-SUB male (RS-232) RX D (2) TXD (3) GND (5) RS-422 9 pin D-SUB male (RS-422) Revision January, 2008, Doc.
  • Page 87 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi FX Series PLC via Computer Link A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller Station number: 0. Control area/status area: D0 / D10. NOTE 1) This communication protocol supports FX series RS485 and RS232 communication module. 2) The default setting of this communication protocol is to support RS485 communication module.
  • Page 88 Contact type Input Relay Output Relay Timer Flag Counter Flag C. Connections (Connector Pinouts) RS-232 DOP Series 9 pin D-SUB male (RS-232) RXD (2) TX D ( 3) GND (5) RS-485 9 pin D-SUB male (RS-485) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Format Word No.
  • Page 89 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Mitsubishi J2s Series Servo A. HMI factory settings Baud rate: 9600, 8, Even, 1 (RS-232). Controller Station number: 0. Control area/status area: None / None. B. Definition of controller Read/Write address Registers Register Type Parameter List (NOTE 1) (cmd: 05/84)
  • Page 90 Contact type Alarm reset (ARST) (NOTE 1) (cmd: NA/82,00) Turn off the external input signals (DI) (OFDI) (NOTE 1) (cmd: NA/90,00) Changes the external output signals (DO) (CHDO) (NOTE 1) (cmd: NA/90,03) Enable the disabled external input signals (ENDI) (NOTE 1) (cmd: NA/90,10) Enable the disabled external output signals (ENDO) (NOTE 1)
  • Page 91 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series MKS BY125 Low Cost Synchrocontroller A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller Station number: 11 Control area/status area: None / None. B. Definition of controller Read/Write address Registers Register Type Data In Register / Setup Register Synchronizing (Differential...
  • Page 92 C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-485 9 pin D-SUB male (RS-485) RXD (2) TXD (3) GND (5) NOTE 1) The valid station number is in the range of 11 to 99. However, 20, 30, 40, 50, 60, 70, 80 and 90 cannot be used as they are all broadcast station number.
  • Page 93 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series (C15, C16, C17). If the data length is out of this range, i.e. occupy other addresses except C0~C17, an error may occur. 6) The effective addresses of Cn are not consecutive (5 blocks: C0~17, C40~41, C45~C48, C50, C90~C92).
  • Page 94 MKS CT150 A. HMI factory settings Baud rate: 9600, 7, E, 1. (RS-232) Controller Station number: 11. Control area/status area: None / None. B. Definition of controller Read/Write address Registers Register Type Data In Register Setup Register Error Count LV Value Printmark Error Batch Counter Waste Counter...
  • Page 95 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-94 Controller 9 pin D-SUB male (RS-232) (3) TXD (2) RXD (5) SG Revision January, 2008, Doc. Name: 2007PDD23000007 Controller 9 pin D-SUB male (RS-232) Pin1...
  • Page 96 MKS MC700/720 Motion Controller A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. Controller Station number: 11 Control area/status area: None / None. B. Definition of controller Read/Write address Registers Register Type General Parameters Parameter Block for Slave 1 Parameter Block for Slave 2 Parameter Block for Slave 3 Parameter Block for Slave 4...
  • Page 97 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 9 pin D-SUB male (RS-232) R XD (2) TX D ( 3) GN D ( 5) RS-422 9 pin D-SUB male (RS-422) R XD - (1 ) R XD + (2) TX D+ (3 ) TX D- (4) RS-485...
  • Page 98 3) Only one data (1 Word/ 1 Double Word / 1 Bit) can be read and written for each communication. So, the “Optimize” (Optimization for reading) selection in “Communication” tab in the “Configuration” dialog box in “Options” menu (Options 4) When using RS-232 communication, the user only can use 3 pins (Pin 2, Pin 3 and Pin 5). DO NOT use 5 pins for RS-232 communication.
  • Page 99 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Modbus(Master) --- 984 RTU / ASCII mode A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. (ASCII) 9600, 8, EVEN, 1. (RTU) Controller station number: 0. Control area/status area: W40100 / W40200. B.
  • Page 100 Modbus Hexadecimal Address (Master) --- RTU / ASCII mode A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. (ASCII) 9600, 8, EVEN, 1. (RTU) Controller station number: 0. Control area/status area: RW-0 / RW-10. NOTE 1) The valid communication address starts from 0 and the format is hexadecimal. So the settable range are 0 to 65535 (i.e.
  • Page 101 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Contacts Contact type Discrete Outputs Discrete Inputs RWB- : can Read and Write. Converting the address to decimal format and plus 1, it will immediately become the corresponding “Standard Modbus” communication address. RB- (Discrete Inputs) : Read only. Converting the address to decimal format and plus 10001, it will immediately become the corresponding “Standard Modbus”...
  • Page 102 Modbus nW (Master) --- RTU / ASCII mode A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. (ASCII) 9600, 8, EVEN, 1. (RTU) Controller station number: 1. Control area/status area: W40100 / W40200. NOTE 1) This driver can read consecutive communication address on the screen via one Modbus command to improve the communication efficiency.
  • Page 103 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Modbus (Slave) --- RTU / ASCII mode A. HMI factory settings Baud rate: 9600, 7, EVEN, 1. (ASCII) 9600, 8, EVEN, 1. (RTU) Controller station number: 0. (Station number is not used in the protocol.) Control area/status area: W40100 / 40200.
  • Page 104 CrossReference Table (Inter Memoryof Delta HMI and Modbus Reference Address) Inter Memory Modbus Reference of Delta HMI 40001 40002 $1023 41024 42001 42002 $M1023 43024 RCPNO 44001 RCP0 45001 RCP1 45002 $2000.0 00001 $2000.1 00002 $2000.15 00016 $2001.0 00017 $2063.0 01009 $2063.15 01024...
  • Page 105 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Inter Memory Modbus Reference of Delta HMI $M200.1 01026 $M200.15 01040 $M201.0 01041 $M263.0 02033 $M263.15 02048 For example: 1. Read internal memory $100 of Delta HMI (HMI station number: 1) : 01 03 00 64 00 01 97 CR LF Write the value of 1000 into internal memory $100 of Delta HMI (HMI station number: 1) : 01 06 00 64 03 E8 AA CR LF 2.
  • Page 106 Modicon TSX Micro (Uni-Telway) A. HMI factory settings Baud rate: 9600, 8, ODD, 1. Controller station number: 2. Control area/status area: %MW0 / %MW10. NOTE 1) HMI station needs to be adjusted to 1 ~ 8. 2) PLC station and HMI station can be the same. 3) The internal memory and relative parameters in PLC should be set properly first.
  • Page 107 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 It needs to use specific cable of Modicon Uni-Telway. (RS-232) --- TSX PCX 1031 9 pin D-SUB male (RS-232) R XD (2) TX D ( 3) GN D ( 5) RS-485 9 pin D-SUB male (RS-485) RXD+ (2)
  • Page 108 Modicon TSX Micro (Modbus RTU) A. HMI factory settings Baud rate: 9600, 8, ODD, 1. Controller station number: 2. Control area/status area: %MW0 / %MW10. NOTE 1) HMI must select Modbus (Master) --- 984 RTU as the communication mode. 2) The communication mode of PLC should be switched to Modbus Slave by using PL7 software. B.
  • Page 109 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Modicon TWIDO Back to Table Its function is the same as Modbus (Master) --- 984 RTU. 1-108 Revision January, 2008, Doc. Name: 2007PDD23000007...
  • Page 110 Moeller PLC A. HMI factory settings Baud rate: 9600, 8, NONE, 1(RS-232). Controller Station number: 2. Control area/status area: MW0/MW10. B. Definition of controller Read/Write address Registers Register Type Marker MW Diagnostic Status DSW Process Status PSW Diagnostic Counter DC Contacts Contact type Marker M...
  • Page 111 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series NOTE 1) Communication Setting The read and write range of register Marker (Device MW) of PS4 Series must be set via PC software or PLC program before connecting to HMI; otherwise, the communication error may occur. The setting range of Marker (Device MW) of PS3 Series is fixed between 0 and 2172 but the address 126 cannot be used.
  • Page 112 NIKKI DENSO NCS-FI/FS Series A. HMI factory settings Baud rate: 9600, 8, ODD, 2. Controller station number: 1. (valid station number: 0 ~ 99) Control area/status area: None. NOTE 1) The valid station number is in the range of 0 to 99. If the station number is out of this range, it will subtracted 100 from itself automatically until the station number is in the valid range.
  • Page 113 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series For example, if setting the starting address as RW900 and the data size is Double Word, the read/write value will be a Double Word which contains RW900(low word) and RW901(high word). In actual application case, if the user sets the data size of RW-n, DW-n as Word, there is no data order reverse problem.
  • Page 114 C. Connections (Connector Pinouts) RS-422 9 pin D-SUB male (RS-422) RXD- (1) RXD+ (2) TXD+ (3) TXD- (4) GND (5) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 14 pin special male (RS-422) (9) TXD (B) (2) TXD (A) (4) RXD (A) (11) RXD (B)
  • Page 115 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Omron C Series PLC A. HMI factory settings Baud rate: 9600, 7, EVEN, 2. Controller station number: 0. Control area/status area: DM0 / DM10. This driver can support OMRON C/CPM series PLC simultaneously. B.
  • Page 116 9 pin D-SUB male (RS-432) R XD (2) TX D ( 3) GN D ( 5) RS-422 9 pin D-SUB male (RS-422) R XD - (1 ) R XD + ( 2) TX D+ (3) TX D- (4) Revision January, 2008, Doc. Name: 2007PDD23000007 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Controller 25 pin D-SUB male (RS-432)
  • Page 117 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Omron CJ1/CS1 Series PLC A. HMI factory settings Baud rate: 9600, 7, EVEN, 2. (RS-232) Controller station number: 0. Control area/status area: D0 / D10. This driver can support OMRON CS/CJ/CP1/CQM/CV/CVM series PLC simultaneously. NOTE The meaning of Communication Error Message: 1) Word Device:...
  • Page 118 CJ1M Models: An: A0-A477 is “read only”. Contacts Contact type CIO area CIOBnbb Hold area HBnbb Auxiliary area ABnbb DM area DBnbb EM area EBm.nbb Timer area Counter area Work area WBnbb EM Current Bank area EMBnbb Index Register IRBnbb DR area DRBnbb TK area...
  • Page 119 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 CJ1M CPU module DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 9 pin D-SUB male (RS-432) R XD (2) TX D ( 3) GN D ( 5) RS-422 9 pin D-SUB male (RS-422)
  • Page 120 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Omron TPM1A PLC Back to Table Its function is the same as Omron C Series PLC. 1-119 Revision January, 2008, Doc. Name: 2007PDD23000007...
  • Page 121 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Siemens S7 200 PLC A. HMI factory settings Baud rate: 9600, 8, EVEN, 1. Controller station number: 2. Control area/status area: VW0 / VW10. B. Definition of controller Read/Write address Register Register Type Timer Analog Input Word Counter...
  • Page 122 Contact type Special S Bit C. Connections (Connector Pinouts) RS-232 via RS-232 / PPI Multi-Master Cable (Connecting DOP series HMI and PPI cable) DOP Series 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) RS-485 via PLC Program Port (RS-485) DOP Series 9 pin D-SUB male (RS-485) RXD+ (2)
  • Page 123 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series Siemens S7 300 PLC (with PC Adapter) A. HMI factory settings Baud rate: 38400, 8, ODD, 1. (RS-232). Controller station number: 2. (Communication via PC adapter, PLC station will not be used, therefore, only 1(HMI) to 1 (PLC) communication is allowed.) Control area/status area: DBW0 / DBW20.
  • Page 124 Register Type Output Image Output Image Internal Bits Internal Bits Data Area Data Area (DB10) Timer Counter NOTE 1) The valid digit number of the value for the T(Timer) and C(Counter) is 3-digits only. Therefore, please enter a 3-digit number. If entering a number that exceeds 3 digits, only the first 3 digits are valid (decimal format).
  • Page 125 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 HMI connects to PC Adaptor 9 pin D-SUB male RXD (2) TXD (3) GND (5) RTS (7) CTS (8) 1-124 Controller 9 pin D-SUB female (3) TXD (2) RXD (5) GND (8) CTS (7) RTS...
  • Page 126 Siemens S7 300 PLC (without PC Adaptor) A. HMI factory settings Baud rate: 19200, 8, EVEN, 1. (RS-485). Controller station number: 2. Control area/status area: DBW0 / DBW20. NOTE 1) Please notice that only 1(HMI) to 1 (PLC) communication is allowed. 2) PLC baud rate should be changed to 19200.
  • Page 127 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series How many COM ports are connected to S7 300 PLC, how may items can be set. 1-126 Revision January, 2008, Doc. Name: 2007PDD23000007...
  • Page 128 B. Definition of controller Read/Write address Register Register Type Input Image Input Image Output Image Output Image Internal Bits Internal Bits Data Area Data Area (DB10) Timer Counter NOTE 1) High Byte of Bit No. The valid digit number of the value for the T(Timer) and C(Counter) is 3-digits only. Therefore, please enter a 3-digit number.
  • Page 129 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series NOTE 2) Low Byte of Bit No. 3) High Byte of Bit No. 4) For all timers, counters and contacts when performing “Multiple Duplicate” function: If it exceeds 65535 when increasing, it will be regarded as 0. If it is less than 0, it will be regarded as 655XX.
  • Page 130 Taian TP02 PLC A. HMI factory settings Baud rate: 19200, 7, None, 1. Controller station number: 1. Control area/status area: V1 / V10. B. Definition of controller Read/Write address Registers Register Type WORD_DEVICE_X WORD_DEVICE_Y WORD_DEVICE_C WORD_DEVICE_V WORD_DEVICE_D WORD_DEVICE_WS WORD_DEVICE_WC WORD_DEVICE_X / WORD_DEVICE_Y / WORD_DEVICE_C: Address must be 1 or the multiple of 16+1.
  • Page 131 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-422 9 pin D-SUB male (RS-422) RXD+ (2) RXD- (1) TXD+ (3) TXD- (4) RS-485 9 pin D-SUB male (RS-232) 1-130 Controller 9 pin D-SUB male (RS-422) (3) TXD+ (8) TXD- (2) RXD+ (7) RXD-...
  • Page 132 Vigor M Series A. HMI factory settings Baud rate: 19200, 7, EVEN, 1. Controller station number: 0. Control area/status area: D0 / D10. NOTE 1) Controller station number: 0 for PROGRAMMER PORT; 1 for COM PORT 2) VB series also can use this driver. B.
  • Page 133 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series C. Connections (Connector Pinouts) RS-232 (PROGRAMMER PORT) 9 pin D-SUB male(RS-232) RXD (2) TXD (3) GND (5) (COM PORT) 9 pin D-SUB male (RS-232) RXD (2) TXD (3) GND (5) 1-132 Controller USB TAPE A Connector (3) TXD (2) RXD (4) GND...
  • Page 134 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series VIPA PLC Back to Table Its function is the same as Siemens S7 300 PLC (with PC Adaptor). 1-133 Revision January, 2008, Doc. Name: 2007PDD23000007...
  • Page 135 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series YOKOGAWA ACE PLC A. HMI factory settings Baud rate: 9600, 8, EVEN, 1. (ASCII code) Controller station number: 1. CPU NO. : 1. Control area/status area: D1 / D10. NOTE 1) CheckSum and End character (CR, LF) are not used during communication. Therefore, the controller should be set to “Not using CheckSum and End character”.
  • Page 136 WORD_DEVICE_I / WORD_DEVICE_E / WORD_DEVICE_L / WORD_DEVICE_M: Address must be 1 or the multiple of 16+1. WORD_DEVICE_X / WORD_DEVICE_Y / WORD_DEVICE_L / WORD_DEVICE_W: Valid address is inconsecutive. Contacts Contact type BIT_DEVICE_X BIT_DEVICE_Y BIT_DEVICE_I BIT_DEVICE_E BIT_DEVICE_L BIT_DEVICE_M BIT_DEVICE_TU BIT_DEVICE_CU BIT_DEVICE_X / BIT_DEVICE_Y : the last two digits of address must be less than 65 (1 ~ 64). BIT_DEVICE_X / BIT _DEVICE_Y / BIT _DEVICE_L : valid address is inconsecutive.
  • Page 137 Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series This page intentionally left blank. 1-136 Revision January, 2008, Doc. Name: 2007PDD23000007...