wattstopper EMTS-100 Installation Instructions

wattstopper EMTS-100 Installation Instructions

Remote test switch

Advertisement

Quick Links

SPECIFICATIONS
Operating voltage ..................................................24VDC, Class 2 device
Contacts ............................SPST, normally closed, momentary contact
Termination ..........................................Flying leads, wire nuts provided
Mounting ................................... Single gang nylon plate, box mounting
Color ................................................................Red button on white plate
DESCRIPTION:
The EMTS-100 consists of a normally closed pushbutton switch on a single
gang face plate. It is intended to be used as a remote test switch for the
Watt Stopper/Legrand ELCU-100 and ECLU-200 Emergency Lighting
Control Units. When properly connected to the ELCU-100, pressing the NC
pushbutton will activate the emergency mode and cause the emergency
fixture(s) to turn on as long as the button is held in. Releasing the button
returns the ELCU-100 or ECLU-200 to normal condition. While in the
normal mode, the emergency lights will be off if the control device is off.
Or, the emergency lights will be on if the control device is on.
INSTALLATION PROCEDURE:
1. Select a location for the EMTS-100 test switch and mount an
appropriate single gang switch box.
2. Connect the two leads from the EMTS-100 to the Remote Out
terminals on the ELCU. This connection is not polarity sensitive.
Note that it will be necessary to remove the factory installed jumper
from the Remote Out terminals on the ELCU.
3. Mount the EMTS plate to the switch box using the screws provided.
4. Test the operation of the EMTS-100 using the test procedure
provided in the installation instructions provided with the ELCU.
EMTS-100
Remote Test Switch
P U
S H
T O
E M
E R
T E S
G E
T
N C
Y L
I G H
T I N
G

Advertisement

loading

Summary of Contents for wattstopper EMTS-100

  • Page 1 Color ..............Red button on white plate DESCRIPTION: The EMTS-100 consists of a normally closed pushbutton switch on a single gang face plate. It is intended to be used as a remote test switch for the Watt Stopper/Legrand ELCU-100 and ECLU-200 Emergency Lighting Control Units.
  • Page 2 (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property, revenue, or profit, or cost of removal, installation or reinstallation.